Changes for page Zūm Discovery

Last modified by Austin Weygandt on 2025/05/02 20:21

From version 38.1
edited by Alexander Mott
on 2025/02/21 18:44
Change comment: There is no comment for this version
To version 5.1
edited by Alexander Mott
on 2022/09/22 21:55
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -Zūm Discovery
1 +Zūm Autodiscovery
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.WebHome
1 +SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.WebHome
Content
... ... @@ -1,14 +9,6 @@
1 -(% class="box errormessage" %)
2 -(((
3 -ūūūūūū**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
4 -
5 -**WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
6 -ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
7 -)))
8 -
9 9  (% class="box warningmessage" %)
10 10  (((
11 -This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
3 +This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Autodiscovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
12 12  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
13 13  )))
14 14  
... ... @@ -16,177 +16,67 @@
16 16  {{toc/}}
17 17  {{/box}}
18 18  
19 -If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a ShowRunnerCLC™ configuration file using the Zūm Discovery feature that is built into ShowRunnerCLC™.
11 +(% class="row" %)
12 +(((
13 +If Zūm Net devices have been configured using Crestron's Zūm App
20 20  
21 -There are certain pre-requisites and limitations when building a ShowRunnerCLC™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
15 += m Wired =
22 22  
23 -= Discovery Filter (ShowRunnerCLC™ 3.062 or newer) =
17 +Lorem
24 24  
25 -Discovered ethernet devices may be filtered using either a hostname or IP Address filter.  The filter is configured from the command line interface.
19 += m Wireless =
26 26  
27 -##+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+
28 -~| Command | Help |
29 -~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|
30 -~| SR discover clear filter | Remove Discovery Filter |
31 -~| SR discover filter | Show Discovery Filter |
32 -~| SR discover filter (X:S) | Set Discovery Filter |
33 -~| - | (X):S:Filter String |
34 -~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|##
21 +As of version 2.190 ShowRunner can discover RF Gateways and attached Zum NETBRIDGES. ShowRunner will find all devices, set them up, create areas and loads.
22 +*Disconnect from the gateway before discovery as they cannot support multiple connections*
23 +*Plug loads do not appear in the UI*
35 35  
36 -=== Hostname Filter ===
25 +== Pre-Requisites: ==
37 37  
38 -The Hostname filter uses a regular expression to filter discovered ZUMNET GATEWAYs or JBOXs.  Multiple expressions can be applied by using a comma to separate the expressions.
39 -
40 -Command Syntax: ##"Type='Hostname' Settings='Expr1[,Expr2]'"##
41 -
42 -Examples:
43 -
44 -1. Only include hostnames that start with ZUMNET-06:
45 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-06'"
46 -1. Include hostnames that start with ZUMNET-FL01 or contain FL03:
47 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-FL01,FL03'"
48 -
49 -=== IP Address Filter ===
50 -
51 -The IP Address filter will restrict discovered ZUMNET GATEWAYs or JBOXs to matching IP Addresses or IP Address ranges.  Multiple addresses and ranges can be used.
52 -
53 -Command Syntax: ##"Type='IPAddress' Settings='Address[,AddressStart-AddressEnd]'"##
54 -
55 -Examples:
56 -
57 -1. Only include a device with an address of 192.168.0.10 or 192.168.0.50:
58 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.10,192.168.0.50'"
59 -1. Include addresses between 192.168.0.11 and 192.168.0.50 and 192.168.0.200 and 192.168.0.240:
60 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.11-192.168.0.50,192.168.0.200-192.168.0.240'"
61 -
62 -=== IP-ID Filter (Added in SR v3.067) ===
63 -
64 -The IP-ID filter will restrict discovered ZUMNET GATEWAYs or JBOXs to matching IP-IDs or IP-ID ranges.  Multiple IDs and ranges can be used.
65 -
66 -Command Syntax: ##"Type='IPID' Settings='IPID[,IPIDStart-IPIDEnd]'"##
67 -
68 -Examples:
69 -
70 -1. Only include a device with an IP-ID of 10 or 5A:
71 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPID' Settings='10,5A'"
72 -1. Include addresses between 11 and 4F and A0 and BF:
73 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPID' Settings='11-4F,A0-BF'"
74 -
75 -= Zūm Wired Discovery =
76 -
77 -== Notes and Limitations ==
78 -
79 -(% class="box warningmessage" %)
80 -(((
81 -* ShowRunnerCLC™ version 3.014 or newer required
82 -* Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
83 -* Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands
84 -* Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
85 -* ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release)
86 -* ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer will discover keypads and set as remote type)
87 -* One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
27 +* Zum NETBRIDGES acquired to their respective gateway (CEN-GWEXER/ZUMNET-GATEWAY)
28 +* SHOWRUNNER™ installed and running on a 3-series processor on the same network as the gateway
29 +* NETBRIDGES do not need to have addresses assigned. SHOWRUNNER™ will automatically address them. If devices all already addressed then their addresses will be honored.
88 88  )))
89 89  
90 -== Steps ==
91 -
92 -1. [[Install ShowRunner™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
93 -1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
94 -1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
95 -1*. Connect to the first ZUMNET-JBOX in Toolbox
96 -1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
97 -1**. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
98 -1**. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
99 -1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
100 -1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
101 -1*. Repeat the above steps for all ZUMNET-JBOXs
102 -1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
103 -1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
104 -1*. Commission room through the app
105 -1**. configure keypad logic
106 -1**. configure occupancy sensor settings
107 -1**. calibrate photocell(s)
108 -1*. Set hostnames for the ZUMNETs.
109 -1**. Zūm discovery will bring in hostnames.
110 -1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
111 -1*. If firmware was out-of-date, then this step should have already been completed
112 -1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
113 -1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
114 -1*. If firmware was out-of-date, then this step should have already been completed
115 -1*. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
116 -1*. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
117 -1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
118 -1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
119 -1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
120 -1*. Full control from ShowRunnerCLC™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between ShowRunnerCLC™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
121 -1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by ShowRunnerCLC™ have static IP addresses and unique CIDs for any hosted devices
122 -1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
123 -1. If trying to Auto Discover on a job with multiple processors or you are returning to a job where new ZUMNET-JBOXs have been added and you only wish to Auto Discover those new devices, ShowRunnerCLC™ 3.062 and newer allow [[filtering based on hostname or IP address>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.Zūm Discovery.WebHome||anchor="HDiscoveryFilter28ShowRunnerCLC21223.062ornewer29"]] in order to limit the devices that are brought into the ShowRunnerCLC™ configuration
124 -1. Run the command: ##sr discover zumnet true true## to add ZUMNET-JBOXs, connected ZUMLINK devices, and some Cresnet devices (such as Cameo keypads) to the configuration. (Note
125 -1*. This command will update the ShowRunnerCLC™ configuration with: 
126 -1**. One area per claimed ZUMNET-JBOX based on the Room Name set in the app
127 -1**. One ZUMNET-BRIDGE load controller per claimed ZUMNET-JBOX to allow the Zūm Room to communicate its current status (scene, occupancy, etc.) to ShowRunnerCLC™
128 -1**. One entry for each ZUMLINK-KP, ZUMLINK-JBOX, and ZUMLINK occupancy sensor connected to each ZUMNET-JBOX
129 -1***. All devices and loads will be auto-labeled based on their connection information, //not// the names they are given in the Zūm App
130 -1***. Keypads will be brought in as "Remote" type and only follow the logic as defined in the Zūm App, allowing for scheduled enabling/disabling of keypads without adding any additional button functions from ShowRunnerCLC™
131 -1***. Occupancy sensors will be brought in with "Use Hardware Logic" and only follow the logic as defined in the Zūm App
132 -1*. Optionally, run ##sr discover zumnet false true## to only add new ZUMLINK devices to the configuration. **Note that previously added ZUMLINK devices will be added again if their CID has been changed**
133 -1*. Run ##sr discover zumnet true false## to add ZUMNET-JBOXs without bringing in any devices. **Note that if a ZUMNET-JBOX already has an entry in its IP Table, ShowRunnerCLC™ will not claim it.** The ZUMNET-JBOX's IP Table must be cleared in order for it to be claimed by the ShowRunnerCLC™ program
134 -1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
135 -1. If new Zūm Link hardware has been added, it is not necessary to do a full Auto Discovery to bring the new devices into ShowRunnerCLC™; instead you can just run ##sr discover zumnet false true## to bring in the new Zūm Link devices without claiming any new Zūm Net devices
136 -
137 -= Zūm Wireless Discovery =
138 -
139 -== Notes and Limitations ==
140 -
141 -(% class="box warningmessage" %)
32 +(% class="box warningmessage" id="HCaution:" %)
142 142  (((
143 -* Processor with ShowRunnerCLC™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
144 -** For ShowRunnerCLC™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
145 -* ZUM-NETBRIDGES must already be acquired to their respective gateway
146 -* ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
147 -* Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
148 -* Plug loads will not appear in the ShowRunnerCLC™ UI
149 -* Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER
34 +**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Autodiscovery
35 +
36 +1. **Manual RF Gateway Assignment** - SHOWRUNNER™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
37 +1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
150 150  )))
151 151  
152 -(% class="box infomessage" id="HCaution:" %)
40 +(% class="row" %)
153 153  (((
154 -**Note:** ShowRunnerCLC™ has two different approaches for Zūm Wireless Discovery
42 +== Manual RF Gateway Claiming ==
155 155  
156 -1. **Manual RF Gateway Assignment** - ShowRunnerCLC™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
157 -1. **Claim All RF Gateways** - ShowRunnerCLC™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different ShowRunnerCLC™ or other Crestron systems on the same local network.
158 -)))
44 +Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
159 159  
160 -== Manual RF Gateway Assignment Instructions ==
161 -
162 -Use this method if you have multiple ShowRunnerCLC™ instances on the same network or have gateways used by other Crestron systems.
163 -
164 164  * Connect to the processor's console with Toolbox or your favorite SSH client.
165 -* Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
166 -* Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
167 -* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step.
168 -* Type ##sr discover zummesh false## and press enter.
47 +* Type "//sr devmgr ethernet query//" and press enter. This queries the local network for RF Gateways.
48 +* Type "//sr devmgr ethernet show devices//" and press enter. This displays all found Crestron ethernet devices.
49 +* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type "//sr ethernet device claim CEN-GWEXER-9E6ADA//". SHOWRUNNER™ will auto-assign an IP-ID. After all gateways have been claimed by SHOWRUNNER™, proceed to the next step.
50 +* Type "//sr discover zum false//" and press enter.
169 169  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
170 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
171 -* Type ##progreset## and press enter to restart ShowRunnerCLC
172 -* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
52 +* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
53 +* Type "//progreset//" and press enter to restart SHOWRUNNER
54 +* Once SHOWRUNNER™ has finished restarting type "//sr discover zum false//" and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
173 173  * Once completed SHOWRUNNER™ is now ready for full Zūm control
174 174  
175 -== Claim All RF Gateways Instructions ==
57 +== Claim All RF Gateways ==
176 176  
177 -Use this method when you have a single ShowRunnerCLC™ instance on a local network with all gateways being used for ShowRunnerCLC™.
59 +Use this method when you have a single SHOWRUNNER™ instance on a local network with all gateways being used for SHOWRUNNER™.
178 178  
179 179  * Connect to the processor's console with Toolbox or your favorite SSH client.
180 -* Type ##sr discover zummesh true## and press enter.
62 +* Type "//sr discover zum true//" and press enter.
181 181  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
182 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
183 -* Type ##progreset## and press enter to restart ShowRunnerCLC
184 -* Once ShowRunnerCLC™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
185 -* Once completed ShowRunnerCLC™ is now ready for full Zūm control
64 +* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
65 +* Type "//progreset//" and press enter to restart SHOWRUNNER
66 +* Once SHOWRUNNER™ has finished restarting type "//sr discover zum false//" and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
67 +* Once completed SHOWRUNNER™ is now ready for full Zūm control
186 186  
187 187  == Examples ==
188 188  
189 -=== Manual Example ===
71 +=== Claim Selectively (Manual) Example ===
190 190  
191 191  {{{MC4>sr devmgr ethernet query
192 192  Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
... ... @@ -205,7 +205,7 @@
205 205  MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
206 206  Claimed ethernet device: CEN-GWEXER-9E6ADA
207 207  MC4>Update request from IP-ID-30 in Program 01
208 -MC4>sr discover zummesh false
90 +MC4>sr discover zum false
209 209  Starting Zum Discovery without gateway claiming
210 210  MC4>Performing Discovery on 1 Gateways.
211 211  Evaluating 3 Devices on Gateway 30
... ... @@ -238,7 +238,7 @@
238 238  MC4>progreset
239 239  ...
240 240  CI ShowRunner startup completed successfully in 8072ms
241 -MC4>sr discover zummesh false
123 +MC4>sr discover zum false
242 242  Starting Zum Discovery without gateway claiming
243 243  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
244 244  Performing Discovery on 1 Gateways.
... ... @@ -291,7 +291,7 @@
291 291  
292 292  === Claim All Example ===
293 293  
294 -{{{MC4>sr discover zummesh true
176 +{{{MC4>sr discover zum true
295 295  Starting Zum Discovery with gateway claiming
296 296  MC4>Found 1 Gateways to check.
297 297  Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
... ... @@ -327,7 +327,7 @@
327 327  MC4>progreset
328 328  ...
329 329  CI ShowRunner startup completed successfully in 8072ms
330 -MC4>sr discover zummesh false
212 +MC4>sr discover zum false
331 331  Starting Zum Discovery without gateway claiming
332 332  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
333 333  Performing Discovery on 1 Gateways.
... ... @@ -378,3 +378,4 @@
378 378  Removed Loads: 0
379 379  Zum Discovery Finished
380 380  }}}