Changes for page Zūm Discovery

Last modified by Alexander Mott on 2025/04/03 17:35

From version 36.1
edited by Alexander Mott
on 2024/10/16 18:07
Change comment: There is no comment for this version
To version 18.1
edited by Alexander Mott
on 2023/04/20 18:39
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.WebHome
1 +SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.WebHome
Content
... ... @@ -1,14 +1,13 @@
1 1  (% class="box errormessage" %)
2 2  (((
3 -**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
3 +WARNING: Cresnet Discovery is not currently working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE.
4 4  
5 -**WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
6 -ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
5 +Downgrade SHOWRUNNER™ to v3.018 in order to auto-discover hardware. SHOWRUNNER™ can be subsequently upgraded once discovery is complete.
7 7  )))
8 8  
9 9  (% class="box warningmessage" %)
10 10  (((
11 -This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
10 +This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Discovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
12 12  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
13 13  )))
14 14  
... ... @@ -16,49 +16,10 @@
16 16  {{toc/}}
17 17  {{/box}}
18 18  
19 -If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a ShowRunnerCLC™ configuration file using the Zūm Discovery feature that is built into ShowRunnerCLC™.
18 +If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Zūm Discovery feature that is built into SHOWRUNNER™.
20 20  
21 -There are certain pre-requisites and limitations when building a ShowRunnerCLC™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
20 +There are certain pre-requisites and limitations when building a SHOWRUNNER™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
22 22  
23 -= Discovery Filter (ShowRunnerCLC™ 3.062 or newer) =
24 -
25 -Discovered ethernet devices may be filtered using either a hostname or IP Address filter.  The filter is configured from the command line interface.
26 -
27 -##+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+
28 -~| Command | Help |
29 -~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|
30 -~| SR discover clear filter | Remove Discovery Filter |
31 -~| SR discover filter | Show Discovery Filter |
32 -~| SR discover filter (X:S) | Set Discovery Filter |
33 -~| - | (X):S:Filter String |
34 -~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|##
35 -
36 -=== Hostname Filter ===
37 -
38 -The Hostname filter uses a regular expression to filter discovered ZUMNET GATEWAYs or JBOXs.  Multiple expressions can be applied by using a comma to separate the expressions.
39 -
40 -Command Syntax: ##"Type='Hostname' Settings='Expr1[,Expr2]'"##
41 -
42 -Examples:
43 -
44 -1. Only include hostnames that start with ZUMNET-06:
45 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-06'"
46 -1. Include hostnames that start with ZUMNET-FL01 or contain FL03:
47 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-FL01,FL03'"
48 -
49 -=== IP Address Filter ===
50 -
51 -The IP Address filter will restrict discovered ZUMNET GATEWAYs or JBOXs to matching IP Addresses or IP Address ranges.  Multiple addresses and ranges can be used.
52 -
53 -Command Syntax: ##"Type='IPAddress' Settings='Address[,AddressStart-AddressEnd]'"##
54 -
55 -Examples:
56 -
57 -1. Only include a device with an address of 192.168.0.10 or 192.168.0.50:
58 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.10,192.168.0.50'"
59 -1. Include addresses between 192.168.0.11 and 192.168.0.50 and 192.168.0.200 and 192.168.0.240:
60 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.11-192.168.0.50,192.168.0.200-192.168.0.240'"
61 -
62 62  = Zūm Wired Discovery =
63 63  
64 64  == Notes and Limitations ==
... ... @@ -65,55 +65,47 @@
65 65  
66 66  (% class="box warningmessage" %)
67 67  (((
68 -* ShowRunnerCLC™ version 3.014 or newer required
28 +* SHOWRUNNER™ version 3.014 or newer required
69 69  * Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
70 -* Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands
30 +* Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
71 71  * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
72 -* ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release)
73 -* ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer will discover keypads and set as remote type)
74 74  * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
75 75  )))
76 76  
77 77  == Steps ==
78 78  
79 -1. [[Install ShowRunner™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
37 +1. [[Install SHOWRUNNER™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
80 80  1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
81 81  1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
82 82  1*. Connect to the first ZUMNET-JBOX in Toolbox
83 83  1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
84 -1**. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
85 -1**. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
42 +1**. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
43 +1**. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
86 86  1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
87 87  1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
88 88  1*. Repeat the above steps for all ZUMNET-JBOXs
89 89  1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
90 -1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
91 -1*. Commission room through the app
92 -1**. configure keypad logic
93 -1**. configure occupancy sensor settings
94 -1**. calibrate photocell(s)
95 -1*. Set hostnames for the ZUMNETs.
96 -1**. Zūm discovery will bring in hostnames.
48 +1. Connect to first ZUMNET-JBOX in the Crestron Zūm App
97 97  1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
98 98  1*. If firmware was out-of-date, then this step should have already been completed
99 99  1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
100 100  1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
101 101  1*. If firmware was out-of-date, then this step should have already been completed
102 -1*. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
103 -1*. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
54 +1*. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
55 +1*. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
104 104  1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
105 105  1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
106 106  1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
107 -1*. Full control from ShowRunnerCLC™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between ShowRunnerCLC™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
108 -1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by ShowRunnerCLC™ have static IP addresses and unique CIDs for any hosted devices
59 +1*. Full control from SHOWRUNNER™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
60 +1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by SHOWRUNNER™ have static IP addresses and unique CIDs for any hosted devices
109 109  1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
110 -1. If trying to Auto Discover on a job with multiple processors or you are returning to a job where new ZUMNET-JBOXs have been added and you only wish to Auto Discover those new devices, ShowRunnerCLC™ 3.062 and newer allow [[filtering based on hostname or IP address>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.Zūm Discovery.WebHome||anchor="HDiscoveryFilter28ShowRunnerCLC21223.062ornewer29"]] in order to limit the devices that are brought into the ShowRunnerCLC™ configuration
62 +1. Run the command: ##sr discover zumnet true false##
63 +1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration
111 111  1. Run the command: ##sr discover zumnet true true##
112 -1*. This command tells ShowRunnerCLC™ to both claim all discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
65 +1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
113 113  1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area
114 114  1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
115 115  1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
116 -1. If new Zūm Link hardware has been added, it is not necessary to do a full Auto Discovery to bring the new devices into ShowRunnerCLC™; instead you can just run ##sr discover zumnet false true## to bring in the new Zūm Link devices without claiming any new Zūm Net devices
117 117  
118 118  = Zūm Wireless Discovery =
119 119  
... ... @@ -121,49 +121,48 @@
121 121  
122 122  (% class="box warningmessage" %)
123 123  (((
124 -* Processor with ShowRunnerCLC™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
125 -** For ShowRunnerCLC™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
76 +* Processor with SHOWRUNNER™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
77 +** For SHOWRUNNER™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
126 126  * ZUM-NETBRIDGES must already be acquired to their respective gateway
127 -* ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
79 +* SHOWRUNNER™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
128 128  * Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
129 -* Plug loads will not appear in the ShowRunnerCLC™ UI
130 -* Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER
81 +* Plug loads will not appear in the SHOWRUNNER™ UI
131 131  )))
132 132  
133 133  (% class="box infomessage" id="HCaution:" %)
134 134  (((
135 -**Note:** ShowRunnerCLC™ has two different approaches for Zūm Wireless Discovery
86 +**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Discovery
136 136  
137 -1. **Manual RF Gateway Assignment** - ShowRunnerCLC™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
138 -1. **Claim All RF Gateways** - ShowRunnerCLC™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different ShowRunnerCLC™ or other Crestron systems on the same local network.
88 +1. **Manual RF Gateway Assignment** - SHOWRUNNER™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
89 +1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
139 139  )))
140 140  
141 141  == Manual RF Gateway Assignment Instructions ==
142 142  
143 -Use this method if you have multiple ShowRunnerCLC™ instances on the same network or have gateways used by other Crestron systems.
94 +Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
144 144  
145 145  * Connect to the processor's console with Toolbox or your favorite SSH client.
146 146  * Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
147 147  * Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
148 -* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step.
99 +* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. SHOWRUNNER™ will auto-assign an IP-ID. After all gateways have been claimed by SHOWRUNNER™, proceed to the next step.
149 149  * Type ##sr discover zummesh false## and press enter.
150 150  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
151 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
152 -* Type ##progreset## and press enter to restart ShowRunnerCLC
153 -* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
102 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
103 +* Type ##progreset## and press enter to restart SHOWRUNNER
104 +* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
154 154  * Once completed SHOWRUNNER™ is now ready for full Zūm control
155 155  
156 156  == Claim All RF Gateways Instructions ==
157 157  
158 -Use this method when you have a single ShowRunnerCLC™ instance on a local network with all gateways being used for ShowRunnerCLC™.
109 +Use this method when you have a single SHOWRUNNER™ instance on a local network with all gateways being used for SHOWRUNNER™.
159 159  
160 160  * Connect to the processor's console with Toolbox or your favorite SSH client.
161 161  * Type ##sr discover zummesh true## and press enter.
162 162  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
163 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
164 -* Type ##progreset## and press enter to restart ShowRunnerCLC
165 -* Once ShowRunnerCLC™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
166 -* Once completed ShowRunnerCLC™ is now ready for full Zūm control
114 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
115 +* Type ##progreset## and press enter to restart SHOWRUNNER
116 +* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
117 +* Once completed SHOWRUNNER™ is now ready for full Zūm control
167 167  