Changes for page Zūm Discovery

Last modified by Austin Weygandt on 2025/05/02 20:21

From version 34.1
edited by Mark Kohlmann
on 2024/10/14 22:00
Change comment: There is no comment for this version
To version 3.1
edited by Alexander Mott
on 2022/09/22 21:47
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -Zūm Discovery
1 +Zūm Autodiscovery
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.WebHome
1 +SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.mark\.kohlmann@chiefintegrations\.com
1 +XWiki.alexander\.mott@chiefintegrations\.com
Content
... ... @@ -1,14 +9,6 @@
1 -(% class="box errormessage" %)
2 -(((
3 -**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
4 -
5 -**WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
6 -ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
7 -)))
8 -
9 9  (% class="box warningmessage" %)
10 10  (((
11 -This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
3 +This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Autodiscovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
12 12  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
13 13  )))
14 14  
... ... @@ -16,179 +16,72 @@
16 16  {{toc/}}
17 17  {{/box}}
18 18  
19 -If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a ShowRunnerCLC™ configuration file using the Zūm Discovery feature that is built into ShowRunnerCLC™.
11 +(% class="row" %)
12 +(((
13 +If Zūm Net devices have been configured using Crestron's Zūm App
20 20  
21 -There are certain pre-requisites and limitations when building a ShowRunnerCLC™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
15 += m Wired =
22 22  
23 -= Discovery Filter (ShowRunnerCLC™ 3.062 or newer) =
17 +Lorem
24 24  
25 -Discovered ethernet devices may be filtered using either a hostname or IP Address filter.  The filter is configured from the command line interface.
19 += m Wireless =
26 26  
27 -##+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+
28 -~| Command | Help |
29 -~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|
30 -~| SR discover clear filter | Remove Discovery Filter |
31 -~| SR discover filter | Show Discovery Filter |
32 -~| SR discover filter (X:S) | Set Discovery Filter |
33 -~| - | (X):S:Filter String |
34 -~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|##
35 35  
36 -=== Hostname Filter ===
22 +As of version 2.190 ShowRunner can discover RF Gateways and attached Zum NETBRIDGES. ShowRunner will find all devices, set them up, create areas and loads.
23 +*Disconnect from the gateway before discovery as they cannot support multiple connections*
24 +*Plug loads do not appear in the UI*
37 37  
38 -The Hostname filter uses a regular expression to filter discovered ZUMNET GATEWAYs or JBOXs.  Multiple expressions can be applied by using a comma to separate the expressions.
26 +== Pre-Requisites: ==
39 39  
40 -Command Syntax: ##"Type='Hostname' Settings='Expr1[,Expr2]'"##
28 +* Zum NETBRIDGES acquired to their respective gateway (CEN-GWEXER/ZUMNET-GATEWAY)
29 +* ShowRunner installed and running on a 3-series processor on the same network as the gateway
30 +* NETBRIDGES do not need to have addresses assigned. ShowRunner will automatically address them. If devices all already addressed then their addresses will be honored.
41 41  
42 -Examples:
43 -
44 -1. Only include hostnames that start with ZUMNET-06:
45 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-06'"
46 -1. Include hostnames that start with ZUMNET-FL01 or contain FL03:
47 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-FL01,FL03'"
48 -
49 -=== IP Address Filter ===
50 -
51 -The IP Address filter will restrict discovered ZUMNET GATEWAYs or JBOXs to matching IP Addresses or IP Address ranges.  Multiple addresses and ranges can be used.
52 -
53 -Command Syntax: ##"Type='IPAddress' Settings='Address[,AddressStart-AddressEnd]'"##
54 -
55 -Examples:
56 -
57 -1. Only include a device with an address of 192.168.0.10 or 192.168.0.50:
58 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.10,192.168.0.50'"
59 -1. Include addresses between 192.168.0.11 and 192.168.0.50 and 192.168.0.200 and 192.168.0.240:
60 -(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.11-192.168.0.50,192.168.0.200-192.168.0.240'"
61 -
62 -= Zūm Wired Discovery =
63 -
64 -== Notes and Limitations ==
65 -
66 -(% class="box warningmessage" %)
32 +(% class="box warningmessage" id="HCaution:" %)
67 67  (((
68 -* ShowRunnerCLC™ version 3.014 or newer required
69 -* Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
70 -* Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands
71 -* Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
72 -* ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release)
73 -* ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer will discover keypads and set as remote type)
74 -* One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
34 +**Note,** SHOWRUNNER has two different types of Zum Wireless autodiscovery:
35 +1. Claim All RF Gateways - ShowRunner will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own.  DO NOT use this method if there are gateways used by different ShowRunner or other Crestron systems on the same local network.
36 +1. Manual RF Gateway Assignment - ShowRunner can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
75 75  )))
76 76  
77 -== Steps ==
39 +== Option 1: Claim All Gateways: ==
78 78  
79 -1. [[Install ShowRunner™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
80 -1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
81 -1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
82 -1*. Connect to the first ZUMNET-JBOX in Toolbox
83 -1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
84 -1**. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
85 -1**. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
86 -1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
87 -1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
88 -1*. Repeat the above steps for all ZUMNET-JBOXs
89 -1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
90 -1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
91 -1*. Commission room through the app
92 -1**. configure keypad logic
93 -1**. configure occupancy sensor settings
94 -1**. calibrate photocell(s)
95 -1*. Set hostnames for the ZUMNETs.
96 -1**. Zūm discovery will bring in hostnames.
97 -1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
98 -1*. If firmware was out-of-date, then this step should have already been completed
99 -1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
100 -1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
101 -1*. If firmware was out-of-date, then this step should have already been completed
102 -1*. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
103 -1*. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
104 -1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
105 -1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
106 -1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
107 -1*. Full control from ShowRunnerCLC™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between ShowRunnerCLC™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
108 -1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by ShowRunnerCLC™ have static IP addresses and unique CIDs for any hosted devices
109 -1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
110 -1. Run the command: ##sr discover zumnet true false##
111 -1*. This command tells ShowRunnerCLC™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration
112 -1. Run the command: ##sr discover zumnet true true##
113 -1*. This command tells ShowRunnerCLC™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
114 -1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area
115 -1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
116 -1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
41 +Use this method when you have a single ShowRunner instance on a local network with all gateways being used for ShowRunner.
117 117  
118 -= Zūm Wireless Discovery =
119 -
120 -== Notes and Limitations ==
121 -
122 -(% class="box warningmessage" %)
123 -(((
124 -* Processor with ShowRunnerCLC™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
125 -** For ShowRunnerCLC™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
126 -* ZUM-NETBRIDGES must already be acquired to their respective gateway
127 -* ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
128 -* Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
129 -* Plug loads will not appear in the ShowRunnerCLC™ UI
130 -* Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER
131 -)))
132 -
133 -(% class="box infomessage" id="HCaution:" %)
134 -(((
135 -**Note:** ShowRunnerCLC™ has two different approaches for Zūm Wireless Discovery
136 -
137 -1. **Manual RF Gateway Assignment** - ShowRunnerCLC™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
138 -1. **Claim All RF Gateways** - ShowRunnerCLC™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different ShowRunnerCLC™ or other Crestron systems on the same local network.
139 -)))
140 -
141 -== Manual RF Gateway Assignment Instructions ==
142 -
143 -Use this method if you have multiple ShowRunnerCLC™ instances on the same network or have gateways used by other Crestron systems.
144 -
145 145  * Connect to the processor's console with Toolbox or your favorite SSH client.
146 -* Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
147 -* Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
148 -* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step.
149 -* Type ##sr discover zummesh false## and press enter.
150 -* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
151 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
152 -* Type ##progreset## and press enter to restart ShowRunnerCLC™
153 -* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
154 -* Once completed SHOWRUNNER™ is now ready for full Zūm control
44 +* Type "//sr discover zum true//" and press enter.
45 +* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
46 +* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunner must be restarted to complete the acquire process.
47 +* Type "//progreset//" and press enter to restart ShowRunner
48 +* Once ShowRunner has finished restarting type "//sr discover zum false//" and press enter. ShowRunner will be able to acquire the loads attached to the Zum rooms at this point.
49 +* Once completed ShowRunner is now ready for full Zum control
155 155  
156 -== Claim All RF Gateways Instructions ==
51 +== Option 2: Manual RF Gateway Claiming: ==
157 157  
158 -Use this method when you have a single ShowRunnerCLC™ instance on a local network with all gateways being used for ShowRunnerCLC™.
53 +Use this method if you have multiple ShowRunner instances on the same network or have gateways used by other Crestron systems.
159 159  
160 160  * Connect to the processor's console with Toolbox or your favorite SSH client.
161 -* Type ##sr discover zummesh true## and press enter.
162 -* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
163 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
164 -* Type ##progreset## and press enter to restart ShowRunnerCLC™
165 -* Once ShowRunnerCLC™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
166 -* Once completed ShowRunnerCLC™ is now ready for full Zūm control
56 +* Type "//sr devmgr ethernet query//" and press enter. This queries the local network for RF Gateways.
57 +* Type "//sr devmgr ethernet show devices//" and press enter. This displays all found Crestron ethernet devices.
58 +* For each gateway that you'd like this instance of ShowRunner to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type "//sr ethernet device claim CEN-GWEXER-9E6ADA//". ShowRunner will auto-assign an IP-ID. After all gateways have been claimed by ShowRunner proceed to the next step.
59 +* Type "//sr discover zum false//" and press enter.
60 +* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
61 +* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunner must be restarted to complete the acquire process.
62 +* Type "//progreset//" and press enter to restart ShowRunner
63 +* Once ShowRunner has finished restarting type "//sr discover zum false//" and press enter. ShowRunner will be able to acquire the loads attached to the Zum rooms at this point.
64 +* Once completed ShowRunner is now ready for full Zum control
167 167  
168 168  == Examples ==
169 169  
170 -=== Manual Example ===
68 +=== Example for Option 1: ===
171 171  
172 -{{{MC4>sr devmgr ethernet query
173 -Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
174 -MC4>sr devmgr ethernet show devices
175 -
176 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
177 -| Adapter | Hostname | IP Address | IP-ID | ID |
178 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
179 -| EthernetLANAdapter | CI-SJC-CEN-CI3-1-COM3 | 10.44.5.20 | 00 | CEN-CI3-1-C3COM-3 [v1.1620.00000, #008436E2] type:1 |
180 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
181 -| EthernetLANAdapter | SB-DIN-CENCN-2 | 10.44.5.81 | 00 | DIN-CENCN-2-POE [v1.3544.00006, #8AB25AA3] |
182 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
183 -| EthernetLANAdapter | CEN-GWEXER-9E6ADA | 10.44.5.120 | 00 | CEN-GWEXER [v1.4230.00015, #848210AD] |
184 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
185 -
186 -MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
187 -Claimed ethernet device: CEN-GWEXER-9E6ADA
188 -MC4>Update request from IP-ID-30 in Program 01
189 -MC4>sr discover zummesh false
190 -Starting Zum Discovery without gateway claiming
191 -MC4>Performing Discovery on 1 Gateways.
70 +{{{MC4>sr discover zum true
71 +Starting Zum Discovery with gateway claiming
72 +MC4>Found 1 Gateways to check.
73 +Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
74 +Update request from IP-ID-30 in Program 01
75 +Claimed 1 Gateways. Waiting for queries to finish.
76 +Performing Discovery on 1 Gateways.
192 192  Evaluating 3 Devices on Gateway 30
193 193  Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
194 194  Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
... ... @@ -199,7 +199,6 @@
199 199  Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
200 200  Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
201 201  Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
202 -Querying cresnet
203 203  Discovering Zum Loads on 1 Gateways.
204 204  Discovering Zum Loads on 3 Devices.
205 205  NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
... ... @@ -219,7 +219,7 @@
219 219  MC4>progreset
220 220  ...
221 221  CI ShowRunner startup completed successfully in 8072ms
222 -MC4>sr discover zummesh false
106 +MC4>sr discover zum false
223 223  Starting Zum Discovery without gateway claiming
224 224  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
225 225  Performing Discovery on 1 Gateways.
... ... @@ -268,17 +268,31 @@
268 268  New Loads: 6
269 269  Modified Loads: 0
270 270  Removed Loads: 0
271 -Zum Discovery Finished}}}
155 +Zum Discovery Finished
156 +}}}
272 272  
273 -=== Claim All Example ===
158 +=== Example for Option 2: ===
274 274  
275 -{{{MC4>sr discover zummesh true
276 -Starting Zum Discovery with gateway claiming
277 -MC4>Found 1 Gateways to check.
278 -Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
279 -Update request from IP-ID-30 in Program 01
280 -Claimed 1 Gateways. Waiting for queries to finish.
281 -Performing Discovery on 1 Gateways.
160 +{{{MC4>sr devmgr ethernet query
161 +Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
162 +MC4>sr devmgr ethernet show devices
163 +
164 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
165 +| Adapter | Hostname | IP Address | IP-ID | ID |
166 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
167 +| EthernetLANAdapter | CI-SJC-CEN-CI3-1-COM3 | 10.44.5.20 | 00 | CEN-CI3-1-C3COM-3 [v1.1620.00000, #008436E2] type:1 |
168 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
169 +| EthernetLANAdapter | SB-DIN-CENCN-2 | 10.44.5.81 | 00 | DIN-CENCN-2-POE [v1.3544.00006, #8AB25AA3] |
170 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
171 +| EthernetLANAdapter | CEN-GWEXER-9E6ADA | 10.44.5.120 | 00 | CEN-GWEXER [v1.4230.00015, #848210AD] |
172 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
173 +
174 +MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
175 +Claimed ethernet device: CEN-GWEXER-9E6ADA
176 +MC4>Update request from IP-ID-30 in Program 01
177 +MC4>sr discover zum false
178 +Starting Zum Discovery without gateway claiming
179 +MC4>Performing Discovery on 1 Gateways.
282 282  Evaluating 3 Devices on Gateway 30
283 283  Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
284 284  Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
... ... @@ -289,6 +289,7 @@
289 289  Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
290 290  Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
291 291  Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
190 +Querying cresnet
292 292  Discovering Zum Loads on 1 Gateways.
293 293  Discovering Zum Loads on 3 Devices.
294 294  NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
... ... @@ -308,7 +308,7 @@
308 308  MC4>progreset
309 309  ...
310 310  CI ShowRunner startup completed successfully in 8072ms
311 -MC4>sr discover zummesh false
210 +MC4>sr discover zum false
312 312  Starting Zum Discovery without gateway claiming
313 313  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
314 314  Performing Discovery on 1 Gateways.
... ... @@ -358,4 +358,5 @@
358 358  Modified Loads: 0
359 359  Removed Loads: 0
360 360  Zum Discovery Finished
361 -}}}
260 + }}}
261 +)))