... ... @@ -1,14 +1,13 @@
1 1  (% class="box errormessage" %)
2 2  (((
3 -**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
3 +WARNING: Cresnet Discovery is not currently working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE.
4 4  
5 -**WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
6 -ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
5 +Downgrade SHOWRUNNER™ to v3.018 in order to auto-discover hardware. SHOWRUNNER™ can be subsequently upgraded once discovery is complete.
7 7  )))
8 8  
9 9  (% class="box warningmessage" %)
10 10  (((
11 -This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
10 +This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Discovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
12 12  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
13 13  )))
14 14  
... ... @@ -16,36 +16,10 @@
16 16  {{toc/}}
17 17  {{/box}}
18 18  
19 -If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a ShowRunnerCLC™ configuration file using the Zūm Discovery feature that is built into ShowRunnerCLC™.
18 +If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Zūm Discovery feature that is built into SHOWRUNNER™.
20 20  
21 -There are certain pre-requisites and limitations when building a ShowRunnerCLC™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
20 +There are certain pre-requisites and limitations when building a SHOWRUNNER™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
22 22  
23 -= Discovery Filter =
24 -
25 -Discovered ethernet devices may be filtered using either a hostname or IP Address filter.  The filter is configured from the command line interface.
26 -
27 -##+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+
28 -~| Command | Help |
29 -~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|
30 -~| SR discover clear filter | Remove Discovery Filter |
31 -~| SR discover filter | Show Discovery Filter |
32 -~| SR discover filter (X:S) | Set Discovery Filter |
33 -~| - | (X):S:Filter String |
34 -~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|##
35 -
36 -=== Hostname Filter ===
37 -
38 -Hostname filter uses a regular expression to filter discovered ZUMNET GATEWAYs or JBOXs.  Multiple expressions can be applied by using a comma to separate the expressions.
39 -
40 -Command Syntax: ##"Type='Hostname' Settings='Expr1[,Expr2]'"##
41 -
42 -Examples:
43 -
44 -1. Only include hostnames that start with ZUMNET-06:
45 -(% style="font-family: Menlo, Monaco, Consolas, Courier New, monospace; white-space: pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-06'"
46 -1. Include hostnames that start with ZUMNET-FL01 or contain FL03:
47 -(% style="font-family: Menlo, Monaco, Consolas, Courier New, monospace; white-space: pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-FL01,FL03'"
48 -
49 49  = Zūm Wired Discovery =
50 50  
51 51  == Notes and Limitations ==
... ... @@ -52,52 +52,44 @@
52 52  
53 53  (% class="box warningmessage" %)
54 54  (((
55 -* ShowRunnerCLC™ version 3.014 or newer required
28 +* SHOWRUNNER™ version 3.014 or newer required
56 56  * Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
57 -* Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands
30 +* Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
58 58  * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
59 -* ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release)
60 -* ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer will discover keypads and set as remote type)
61 61  * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
62 62  )))
63 63  
64 64  == Steps ==
65 65  
66 -1. [[Install ShowRunner™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
37 +1. [[Install SHOWRUNNER™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
67 67  1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
68 68  1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
69 69  1*. Connect to the first ZUMNET-JBOX in Toolbox
70 70  1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
71 -1**. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
72 -1**. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
42 +1**. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
43 +1**. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
73 73  1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
74 74  1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
75 75  1*. Repeat the above steps for all ZUMNET-JBOXs
76 76  1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
77 -1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
78 -1*. Commission room through the app
79 -1**. configure keypad logic
80 -1**. configure occupancy sensor settings
81 -1**. calibrate photocell(s)
82 -1*. Set hostnames for the ZUMNETs.
83 -1**. Zūm discovery will bring in hostnames.
48 +1. Connect to first ZUMNET-JBOX in the Crestron Zūm App
84 84  1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
85 85  1*. If firmware was out-of-date, then this step should have already been completed
86 86  1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
87 87  1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
88 88  1*. If firmware was out-of-date, then this step should have already been completed
89 -1*. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
90 -1*. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
54 +1*. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
55 +1*. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
91 91  1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
92 92  1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
93 93  1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
94 -1*. Full control from ShowRunnerCLC™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between ShowRunnerCLC™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
95 -1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by ShowRunnerCLC™ have static IP addresses and unique CIDs for any hosted devices
59 +1*. Full control from SHOWRUNNER™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
60 +1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by SHOWRUNNER™ have static IP addresses and unique CIDs for any hosted devices
96 96  1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
97 97  1. Run the command: ##sr discover zumnet true false##
98 -1*. This command tells ShowRunnerCLC™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration
63 +1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration
99 99  1. Run the command: ##sr discover zumnet true true##
100 -1*. This command tells ShowRunnerCLC™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
65 +1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
101 101  1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area
102 102  1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
103 103  1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
... ... @@ -108,49 +108,48 @@
108 108  
109 109  (% class="box warningmessage" %)
110 110  (((
111 -* Processor with ShowRunnerCLC™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
112 -** For ShowRunnerCLC™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
76 +* Processor with SHOWRUNNER™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
77 +** For SHOWRUNNER™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
113 113  * ZUM-NETBRIDGES must already be acquired to their respective gateway
114 -* ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
79 +* SHOWRUNNER™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
115 115  * Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
116 -* Plug loads will not appear in the ShowRunnerCLC™ UI
117 -* Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER
81 +* Plug loads will not appear in the SHOWRUNNER™ UI
118 118  )))
119 119  
120 120  (% class="box infomessage" id="HCaution:" %)
121 121  (((
122 -**Note:** ShowRunnerCLC™ has two different approaches for Zūm Wireless Discovery
86 +**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Discovery
123 123  
124 -1. **Manual RF Gateway Assignment** - ShowRunnerCLC™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
125 -1. **Claim All RF Gateways** - ShowRunnerCLC™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different ShowRunnerCLC™ or other Crestron systems on the same local network.
88 +1. **Manual RF Gateway Assignment** - SHOWRUNNER™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
89 +1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
126 126  )))
127 127  
128 128  == Manual RF Gateway Assignment Instructions ==
129 129  
130 -Use this method if you have multiple ShowRunnerCLC™ instances on the same network or have gateways used by other Crestron systems.
94 +Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
131 131  
132 132  * Connect to the processor's console with Toolbox or your favorite SSH client.
133 133  * Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
134 134  * Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
135 -* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step.
99 +* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. SHOWRUNNER™ will auto-assign an IP-ID. After all gateways have been claimed by SHOWRUNNER™, proceed to the next step.
136 136  * Type ##sr discover zummesh false## and press enter.
137 137  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
138 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
139 -* Type ##progreset## and press enter to restart ShowRunnerCLC
140 -* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
102 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
103 +* Type ##progreset## and press enter to restart SHOWRUNNER
104 +* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
141 141  * Once completed SHOWRUNNER™ is now ready for full Zūm control
142 142  
143 143  == Claim All RF Gateways Instructions ==
144 144  
145 -Use this method when you have a single ShowRunnerCLC™ instance on a local network with all gateways being used for ShowRunnerCLC™.
109 +Use this method when you have a single SHOWRUNNER™ instance on a local network with all gateways being used for SHOWRUNNER™.
146 146  
147 147  * Connect to the processor's console with Toolbox or your favorite SSH client.
148 148  * Type ##sr discover zummesh true## and press enter.
149 149  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
150 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
151 -* Type ##progreset## and press enter to restart ShowRunnerCLC
152 -* Once ShowRunnerCLC™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
153 -* Once completed ShowRunnerCLC™ is now ready for full Zūm control
114 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
115 +* Type ##progreset## and press enter to restart SHOWRUNNER
116 +* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
117 +* Once completed SHOWRUNNER™ is now ready for full Zūm control
154 154  
155 155  == Examples ==
156 156