Changes for page Zūm Discovery

Last modified by Austin Weygandt on 2025/05/02 20:21

From version 24.2
edited by Craig Lewis
on 2024/05/22 21:45
Change comment: There is no comment for this version
To version 2.1
edited by Alexander Mott
on 2022/09/22 21:44
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -Zūm Discovery
1 +Zūm Autodiscovery
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.WebHome
1 +SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.craig\.lewis@chiefintegrations\.com
1 +XWiki.alexander\.mott@chiefintegrations\.com
Content
... ... @@ -1,14 +9,6 @@
1 -(% class="box errormessage" %)
2 -(((
3 -**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
4 -
5 -**WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
6 -ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
7 -)))
8 -
9 9  (% class="box warningmessage" %)
10 10  (((
11 -This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
3 +This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Autodiscovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
12 12  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
13 13  )))
14 14  
... ... @@ -16,136 +16,71 @@
16 16  {{toc/}}
17 17  {{/box}}
18 18  
19 -If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a ShowRunnerCLC™ configuration file using the Zūm Discovery feature that is built into ShowRunnerCLC™.
11 +(% class="row" %)
12 +(((
13 +If Zūm Net devices have been configured using Crestron's Zūm App
20 20  
21 -There are certain pre-requisites and limitations when building a ShowRunnerCLC™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
15 += m Wired =
22 22  
23 -= Zūm Wired Discovery =
17 +Lorem
24 24  
25 -== Notes and Limitations ==
19 += Zūm Wireless =
26 26  
27 -(% class="box warningmessage" %)
28 -(((
29 -* ShowRunnerCLC™ version 3.014 or newer required
30 -* Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
31 -* Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
32 -* Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
33 -* One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
34 -)))
35 35  
36 -== Steps ==
22 +As of version 2.190 ShowRunner can discover RF Gateways and attached Zum NETBRIDGES. ShowRunner will find all devices, set them up, create areas and loads.
23 +*Disconnect from the gateway before discovery as they cannot support multiple connections*
24 +*Plug loads do not appear in the UI*
37 37  
38 -1. [[Install ShowRunner™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
39 -1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
40 -1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
41 -1*. Connect to the first ZUMNET-JBOX in Toolbox
42 -1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
43 -1**. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
44 -1**. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
45 -1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
46 -1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
47 -1*. Repeat the above steps for all ZUMNET-JBOXs
48 -1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
49 -1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
50 -1*. Commission room through the app
51 -1**. configure keypad logic
52 -1**. configure occupancy sensor settings
53 -1**. calibrate photocell(s)
54 -1*. Set hostnames for the ZUMNETs for easy identification when hardware is discovered.
55 -1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
56 -1*. If firmware was out-of-date, then this step should have already been completed
57 -1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
58 -1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
59 -1*. If firmware was out-of-date, then this step should have already been completed
60 -1*. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
61 -1*. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
62 -1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
63 -1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
64 -1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
65 -1*. Full control from ShowRunnerCLC™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between ShowRunnerCLC™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
66 -1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by ShowRunnerCLC™ have static IP addresses and unique CIDs for any hosted devices
67 -1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
68 -1. Run the command: ##sr discover zumnet true false##
69 -1*. This command tells ShowRunnerCLC™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration
70 -1. Run the command: ##sr discover zumnet true true##
71 -1*. This command tells ShowRunnerCLC™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
72 -1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area
73 -1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
74 -1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
26 +== **Pre-Requisites:** ==
75 75  
76 -= Zūm Wireless Discovery =
28 +* Zum NETBRIDGES acquired to their respective gateway (CEN-GWEXER/ZUMNET-GATEWAY)
29 +* ShowRunner installed and running on a 3-series processor on the same network as the gateway
30 +* NETBRIDGES do not need to have addresses assigned. ShowRunner will automatically address them. If devices all already addressed then their addresses will be honored.
77 77  
78 -== Notes and Limitations ==
32 +=== **Caution:** ===
79 79  
80 -(% class="box warningmessage" %)
81 -(((
82 -* Processor with ShowRunnerCLC™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
83 -** For ShowRunnerCLC™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
84 -* ZUM-NETBRIDGES must already be acquired to their respective gateway
85 -* ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
86 -* Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
87 -* Plug loads will not appear in the ShowRunnerCLC™ UI
88 -)))
34 +* ShowRunner has 2 discovery approaches.
35 +** Option 1: Claim All RF Gateways - ShowRunner will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. DO NOT use this method if there are gateways used by different ShowRunner or other Crestron systems on the same local network.
36 +** Option 2: Manual RF Gateway Assignment - ShowRunner can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
89 89  
90 -(% class="box infomessage" id="HCaution:" %)
91 -(((
92 -**Note:** ShowRunnerCLC™ has two different approaches for Zūm Wireless Discovery
38 +== Option 1: Claim All Gateways: ==
93 93  
94 -1. **Manual RF Gateway Assignment** - ShowRunnerCLC™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
95 -1. **Claim All RF Gateways** - ShowRunnerCLC™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different ShowRunnerCLC™ or other Crestron systems on the same local network.
96 -)))
40 +Use this method when you have a single ShowRunner instance on a local network with all gateways being used for ShowRunner.
97 97  
98 -== Manual RF Gateway Assignment Instructions ==
99 -
100 -Use this method if you have multiple ShowRunnerCLC™ instances on the same network or have gateways used by other Crestron systems.
101 -
102 102  * Connect to the processor's console with Toolbox or your favorite SSH client.
103 -* Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
104 -* Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
105 -* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step.
106 -* Type ##sr discover zummesh false## and press enter.
107 -* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
108 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
109 -* Type ##progreset## and press enter to restart ShowRunnerCLC™
110 -* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
111 -* Once completed SHOWRUNNER™ is now ready for full Zūm control
43 +* Type "//sr discover zum true//" and press enter.
44 +* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
45 +* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunner must be restarted to complete the acquire process.
46 +* Type "//progreset//" and press enter to restart ShowRunner
47 +* Once ShowRunner has finished restarting type "//sr discover zum false//" and press enter. ShowRunner will be able to acquire the loads attached to the Zum rooms at this point.
48 +* Once completed ShowRunner is now ready for full Zum control
112 112  
113 -== Claim All RF Gateways Instructions ==
50 +== Option 2: Manual RF Gateway Claiming: ==
114 114  
115 -Use this method when you have a single ShowRunnerCLC™ instance on a local network with all gateways being used for ShowRunnerCLC™.
52 +Use this method if you have multiple ShowRunner instances on the same network or have gateways used by other Crestron systems.
116 116  
117 117  * Connect to the processor's console with Toolbox or your favorite SSH client.
118 -* Type ##sr discover zummesh true## and press enter.
119 -* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
120 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
121 -* Type ##progreset## and press enter to restart ShowRunnerCLC™
122 -* Once ShowRunnerCLC™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
123 -* Once completed ShowRunnerCLC™ is now ready for full Zūm control
55 +* Type "//sr devmgr ethernet query//" and press enter. This queries the local network for RF Gateways.
56 +* Type "//sr devmgr ethernet show devices//" and press enter. This displays all found Crestron ethernet devices.
57 +* For each gateway that you'd like this instance of ShowRunner to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type "//sr ethernet device claim CEN-GWEXER-9E6ADA//". ShowRunner will auto-assign an IP-ID. After all gateways have been claimed by ShowRunner proceed to the next step.
58 +* Type "//sr discover zum false//" and press enter.
59 +* Status messages and the results will be displayed on the console. The process should take about 3 minutes.
60 +* When the discovery is finished type "//sr save//" and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunner must be restarted to complete the acquire process.
61 +* Type "//progreset//" and press enter to restart ShowRunner
62 +* Once ShowRunner has finished restarting type "//sr discover zum false//" and press enter. ShowRunner will be able to acquire the loads attached to the Zum rooms at this point.
63 +* Once completed ShowRunner is now ready for full Zum control
124 124  
125 125  == Examples ==
126 126  
127 -=== Manual Example ===
67 +=== Example for Option 1: ===
128 128  
129 -{{{MC4>sr devmgr ethernet query
130 -Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
131 -MC4>sr devmgr ethernet show devices
132 -
133 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
134 -| Adapter | Hostname | IP Address | IP-ID | ID |
135 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
136 -| EthernetLANAdapter | CI-SJC-CEN-CI3-1-COM3 | 10.44.5.20 | 00 | CEN-CI3-1-C3COM-3 [v1.1620.00000, #008436E2] type:1 |
137 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
138 -| EthernetLANAdapter | SB-DIN-CENCN-2 | 10.44.5.81 | 00 | DIN-CENCN-2-POE [v1.3544.00006, #8AB25AA3] |
139 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
140 -| EthernetLANAdapter | CEN-GWEXER-9E6ADA | 10.44.5.120 | 00 | CEN-GWEXER [v1.4230.00015, #848210AD] |
141 -+--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
142 -
143 -MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
144 -Claimed ethernet device: CEN-GWEXER-9E6ADA
145 -MC4>Update request from IP-ID-30 in Program 01
146 -MC4>sr discover zummesh false
147 -Starting Zum Discovery without gateway claiming
148 -MC4>Performing Discovery on 1 Gateways.
69 +{{{MC4>sr discover zum true
70 +Starting Zum Discovery with gateway claiming
71 +MC4>Found 1 Gateways to check.
72 +Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
73 +Update request from IP-ID-30 in Program 01
74 +Claimed 1 Gateways. Waiting for queries to finish.
75 +Performing Discovery on 1 Gateways.
149 149  Evaluating 3 Devices on Gateway 30
150 150  Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
151 151  Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
... ... @@ -156,7 +156,6 @@
156 156  Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
157 157  Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
158 158  Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
159 -Querying cresnet
160 160  Discovering Zum Loads on 1 Gateways.
161 161  Discovering Zum Loads on 3 Devices.
162 162  NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
... ... @@ -176,7 +176,7 @@
176 176  MC4>progreset
177 177  ...
178 178  CI ShowRunner startup completed successfully in 8072ms
179 -MC4>sr discover zummesh false
105 +MC4>sr discover zum false
180 180  Starting Zum Discovery without gateway claiming
181 181  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
182 182  Performing Discovery on 1 Gateways.
... ... @@ -225,17 +225,31 @@
225 225  New Loads: 6
226 226  Modified Loads: 0
227 227  Removed Loads: 0
228 -Zum Discovery Finished}}}
154 +Zum Discovery Finished
155 +}}}
229 229  
230 -=== Claim All Example ===
157 +=== Example for Option 2: ===
231 231  
232 -{{{MC4>sr discover zummesh true
233 -Starting Zum Discovery with gateway claiming
234 -MC4>Found 1 Gateways to check.
235 -Claimed Gateway SN: 1720JBH04269 at IP-ID: 30
236 -Update request from IP-ID-30 in Program 01
237 -Claimed 1 Gateways. Waiting for queries to finish.
238 -Performing Discovery on 1 Gateways.
159 +{{{MC4>sr devmgr ethernet query
160 +Ethrenet AutoDiscovery Result: AutoDiscoveryOperationSuccess
161 +MC4>sr devmgr ethernet show devices
162 +
163 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
164 +| Adapter | Hostname | IP Address | IP-ID | ID |
165 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
166 +| EthernetLANAdapter | CI-SJC-CEN-CI3-1-COM3 | 10.44.5.20 | 00 | CEN-CI3-1-C3COM-3 [v1.1620.00000, #008436E2] type:1 |
167 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
168 +| EthernetLANAdapter | SB-DIN-CENCN-2 | 10.44.5.81 | 00 | DIN-CENCN-2-POE [v1.3544.00006, #8AB25AA3] |
169 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
170 +| EthernetLANAdapter | CEN-GWEXER-9E6ADA | 10.44.5.120 | 00 | CEN-GWEXER [v1.4230.00015, #848210AD] |
171 ++--------------------+-------------------------------+-------------+-------+----------------------------------------------------------------------------------+
172 +
173 +MC4>sr ethernet device claim CEN-GWEXER-9E6ADA
174 +Claimed ethernet device: CEN-GWEXER-9E6ADA
175 +MC4>Update request from IP-ID-30 in Program 01
176 +MC4>sr discover zum false
177 +Starting Zum Discovery without gateway claiming
178 +MC4>Performing Discovery on 1 Gateways.
239 239  Evaluating 3 Devices on Gateway 30
240 240  Claiming ZUM-NETBRIDGE SN: 1726NEJ01096 from IP-ID: 30
241 241  Dev: ZUM-NETBRIDGE addrssing to RF ID: 03
... ... @@ -246,6 +246,7 @@
246 246  Claiming ZUM-NETBRIDGE SN: 1914NEJ03098 from IP-ID: 30
247 247  Dev: ZUM-NETBRIDGE addrssing to RF ID: 05
248 248  Setting up RF Device 'ZUM-NETBRIDGE' on Gateway 30 at RF-ID 05
189 +Querying cresnet
249 249  Discovering Zum Loads on 1 Gateways.
250 250  Discovering Zum Loads on 3 Devices.
251 251  NETBIRDGE: NewLoads: 0 ModifiedLoads: 0 RemovedLoads: 0
... ... @@ -265,7 +265,7 @@
265 265  MC4>progreset
266 266  ...
267 267  CI ShowRunner startup completed successfully in 8072ms
268 -MC4>sr discover zummesh false
209 +MC4>sr discover zum false
269 269  Starting Zum Discovery without gateway claiming
270 270  MC4>Notice: SimplSharpPro[App01] # 2020-07-21 22:19:46 # Recalling startup scenes (if applicable)
271 271  Performing Discovery on 1 Gateways.
... ... @@ -315,4 +315,5 @@
315 315  Modified Loads: 0
316 316  Removed Loads: 0
317 317  Zum Discovery Finished
318 -}}}
259 + }}}
260 +)))