Changes for page Zūm Discovery

Last modified by Alexander Mott on 2025/04/03 17:35

From version 23.1
edited by Alexander Mott
on 2023/12/12 18:30
Change comment: There is no comment for this version
To version 31.1
edited by Craig Lewis
on 2024/09/30 17:35
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.WebHome
1 +SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.alexander\.mott@chiefintegrations\.com
1 +XWiki.craig\.lewis@chiefintegrations\.com
Content
... ... @@ -8,7 +8,7 @@
8 8  
9 9  (% class="box warningmessage" %)
10 10  (((
11 -This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
11 +This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
12 12  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
13 13  )))
14 14  
... ... @@ -28,8 +28,10 @@
28 28  (((
29 29  * ShowRunnerCLC™ version 3.014 or newer required
30 30  * Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
31 -* Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
31 +* Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands
32 32  * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
33 +* ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release)
34 +* ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer)
33 33  * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
34 34  )))
35 35  
... ... @@ -46,7 +46,13 @@
46 46  1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
47 47  1*. Repeat the above steps for all ZUMNET-JBOXs
48 48  1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
49 -1. Connect to first ZUMNET-JBOX in the Crestron Zūm App
51 +1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
52 +1*. Commission room through the app
53 +1**. configure keypad logic
54 +1**. configure occupancy sensor settings
55 +1**. calibrate photocell(s)
56 +1*. Set hostnames for the ZUMNETs.
57 +1**. Zūm discovery will bring in hostnames.
50 50  1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
51 51  1*. If firmware was out-of-date, then this step should have already been completed
52 52  1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
... ... @@ -80,6 +80,7 @@
80 80  * ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
81 81  * Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
82 82  * Plug loads will not appear in the ShowRunnerCLC™ UI
91 +* Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER
83 83  )))
84 84  
85 85  (% class="box infomessage" id="HCaution:" %)