Changes for page Zūm Discovery

Last modified by Alexander Mott on 2025/04/03 17:35

From version 22.1
edited by Alexander Mott
on 2023/12/08 18:34
Change comment: There is no comment for this version
To version 32.1
edited by Craig Lewis
on 2024/09/30 17:35
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.WebHome
1 +SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.alexander\.mott@chiefintegrations\.com
1 +XWiki.craig\.lewis@chiefintegrations\.com
Content
... ... @@ -1,17 +1,14 @@
1 1  (% class="box errormessage" %)
2 2  (((
3 +**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
4 +
3 3  **WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
4 4  ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
5 5  )))
6 6  
7 -(% class="box errormessage" %)
8 -(((
9 -**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
10 -)))
11 -
12 12  (% class="box warningmessage" %)
13 13  (((
14 -This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
11 +This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
15 15  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
16 16  )))
17 17  
... ... @@ -31,8 +31,10 @@
31 31  (((
32 32  * ShowRunnerCLC™ version 3.014 or newer required
33 33  * Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
34 -* Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
31 +* Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands
35 35  * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
33 +* ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release)
34 +* ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer will discover keypads and set as remote type)
36 36  * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
37 37  )))
38 38  
... ... @@ -49,7 +49,13 @@
49 49  1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
50 50  1*. Repeat the above steps for all ZUMNET-JBOXs
51 51  1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
52 -1. Connect to first ZUMNET-JBOX in the Crestron Zūm App
51 +1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
52 +1*. Commission room through the app
53 +1**. configure keypad logic
54 +1**. configure occupancy sensor settings
55 +1**. calibrate photocell(s)
56 +1*. Set hostnames for the ZUMNETs.
57 +1**. Zūm discovery will bring in hostnames.
53 53  1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
54 54  1*. If firmware was out-of-date, then this step should have already been completed
55 55  1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
... ... @@ -83,6 +83,7 @@
83 83  * ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
84 84  * Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
85 85  * Plug loads will not appear in the ShowRunnerCLC™ UI
91 +* Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER
86 86  )))
87 87  
88 88  (% class="box infomessage" id="HCaution:" %)