Changes for page Zūm Discovery

Last modified by Alexander Mott on 2025/04/03 17:35

From version 22.1
edited by Alexander Mott
on 2023/12/08 18:34
Change comment: There is no comment for this version
To version 20.1
edited by Alexander Mott
on 2023/10/11 16:36
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,12 +1,13 @@
1 1  (% class="box errormessage" %)
2 2  (((
3 -**WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
4 -ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
3 +WARNING: Cresnet Discovery is not currently working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE.
4 +
5 +Downgrade ShowRunnerCLC™ to v3.018 in order to auto-discover hardware. ShowRunnerCLC™ can be subsequently upgraded once discovery is complete.
5 5  )))
6 6  
7 7  (% class="box errormessage" %)
8 8  (((
9 -**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
10 +IMPORTANT: When using ShowRunnerCLC™ with a ZUM-HUB4, do not discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
10 10  )))
11 11  