Changes for page Zūm Discovery

Last modified by Austin Weygandt on 2025/05/02 20:21

From version 17.1
edited by Alexander Mott
on 2023/03/29 21:28
Change comment: There is no comment for this version
To version 38.1
edited by Alexander Mott
on 2025/02/21 18:44
Change comment: There is no comment for this version

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Device Addressing.WebHome
1 +SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.WebHome
Content
... ... @@ -1,11 +1,14 @@
1 1  (% class="box errormessage" %)
2 2  (((
3 -WARNING: Cresnet Discovery is not currently working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE. Discovery must be fixed before SHOWRUNNER™ can auto-discover hardware.
3 +ūūūūūū**IMPORTANT:** When using ShowRunnerCLC™ with a ZUM-HUB4, **do not** discover Zūm Rooms using the Crestron HUB4 Web UI. During discovery, the HUB4 will claim ZUMNET-JBOXs and prevent ShowRunnerCLC™ from auto-discovering or registering the Zūm hardware for itself.
4 +
5 +**WARNING:** Cresnet Discovery is non-functional for ZUMNET-JBOXs with certain versions of Crestron Device Database.
6 +ShowRunnerCLC™ versions v3.019 through v3.041 must be either downgraded to v3.018 or upgraded to v3.042 or newer in order to perform auto-discover functions.
4 4  )))
5 5  
6 6  (% class="box warningmessage" %)
7 7  (((
8 -This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Discovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
11 +This article is about automatically building a ShowRunnerCLC™ configuration using the Zūm Discovery feature of ShowRunnerCLC™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Zūm App Overview.WebHome]].
9 9  For instructions on configuring Zūm Net devices using Crestron Toolbox, see [[this page>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.ZUMNET-JBOX Setup.WebHome]].
10 10  )))
11 11  
... ... @@ -13,10 +13,62 @@
13 13  {{toc/}}
14 14  {{/box}}
15 15  
16 -If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Zūm Discovery feature that is built into SHOWRUNNER™.
19 +If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a ShowRunnerCLC™ configuration file using the Zūm Discovery feature that is built into ShowRunnerCLC™.
17 17  
18 -There are certain pre-requisites and limitations when building a SHOWRUNNER™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
21 +There are certain pre-requisites and limitations when building a ShowRunnerCLC™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
19 19  
23 += Discovery Filter (ShowRunnerCLC™ 3.062 or newer) =
24 +
25 +Discovered ethernet devices may be filtered using either a hostname or IP Address filter.  The filter is configured from the command line interface.
26 +
27 +##+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-+
28 +~| Command | Help |
29 +~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|
30 +~| SR discover clear filter | Remove Discovery Filter |
31 +~| SR discover filter | Show Discovery Filter |
32 +~| SR discover filter (X:S) | Set Discovery Filter |
33 +~| - | (X):S:Filter String |
34 +~|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-~-|##
35 +
36 +=== Hostname Filter ===
37 +
38 +The Hostname filter uses a regular expression to filter discovered ZUMNET GATEWAYs or JBOXs.  Multiple expressions can be applied by using a comma to separate the expressions.
39 +
40 +Command Syntax: ##"Type='Hostname' Settings='Expr1[,Expr2]'"##
41 +
42 +Examples:
43 +
44 +1. Only include hostnames that start with ZUMNET-06:
45 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-06'"
46 +1. Include hostnames that start with ZUMNET-FL01 or contain FL03:
47 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='Hostname' Settings='^ZUMNET-FL01,FL03'"
48 +
49 +=== IP Address Filter ===
50 +
51 +The IP Address filter will restrict discovered ZUMNET GATEWAYs or JBOXs to matching IP Addresses or IP Address ranges.  Multiple addresses and ranges can be used.
52 +
53 +Command Syntax: ##"Type='IPAddress' Settings='Address[,AddressStart-AddressEnd]'"##
54 +
55 +Examples:
56 +
57 +1. Only include a device with an address of 192.168.0.10 or 192.168.0.50:
58 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.10,192.168.0.50'"
59 +1. Include addresses between 192.168.0.11 and 192.168.0.50 and 192.168.0.200 and 192.168.0.240:
60 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPAddress' Settings='192.168.0.11-192.168.0.50,192.168.0.200-192.168.0.240'"
61 +
62 +=== IP-ID Filter (Added in SR v3.067) ===
63 +
64 +The IP-ID filter will restrict discovered ZUMNET GATEWAYs or JBOXs to matching IP-IDs or IP-ID ranges.  Multiple IDs and ranges can be used.
65 +
66 +Command Syntax: ##"Type='IPID' Settings='IPID[,IPIDStart-IPIDEnd]'"##
67 +
68 +Examples:
69 +
70 +1. Only include a device with an IP-ID of 10 or 5A:
71 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPID' Settings='10,5A'"
72 +1. Include addresses between 11 and 4F and A0 and BF:
73 +(% style="font-family:Menlo,Monaco,Consolas,Courier New,monospace; white-space:pre" %)sr discover filter "Type='IPID' Settings='11-4F,A0-BF'"
74 +
20 20  = Zūm Wired Discovery =
21 21  
22 22  == Notes and Limitations ==
... ... @@ -23,47 +23,61 @@
23 23  
24 24  (% class="box warningmessage" %)
25 25  (((
26 -* SHOWRUNNER™ version 3.014 or newer required
81 +* ShowRunnerCLC™ version 3.014 or newer required
27 27  * Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
28 -* Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
83 +* Disconnect from any ZUMNET devices you may be connected to in Toolbox and confirm all hardware (NETs and LINKs) are online prior to running the discovery commands
29 29  * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
85 +* ZUMLINK-IOs will not be discovered (Expected to be discoverable in future ShowRunnerCLC™ release)
86 +* ZUMLINK-KPs will not be discovered on older versions of ShowRunnerCLC™ (v3.058 or newer will discover keypads and set as remote type)
30 30  * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
31 31  )))
32 32  
33 33  == Steps ==
34 34  
35 -1. [[Install SHOWRUNNER™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
92 +1. [[Install ShowRunner™>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.SHOWRUNNER™ Installation and Network Setup.WebHome]] on the processor and configure the processor as necessary
36 36  1*. Note that while Zūm Wired discovery will build a configuration, if a configuration file was provided then it should still be loaded as it may contain location data or non-Zūm devices.
37 37  1. If the ZUMNET-JBOX firmware is too out-of-date to connect using the Crestron Zūm App, then there are some additional steps required: 
38 38  1*. Connect to the first ZUMNET-JBOX in Toolbox
39 39  1*. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
40 -1**. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
41 -1**. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
97 +1**. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
98 +1**. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
42 42  1*. Set unique Connection IDs for each device hosted on the ZUMNET-JBOX so that their firmware can be updated
43 43  1*. Load the Zūm Wired firmware to the ZUMNET-JBOX
44 44  1*. Repeat the above steps for all ZUMNET-JBOXs
45 45  1*. Once all the ZUMNET-JBOXs have pushed the new firmware to their hosted devices, disconnect from them in Toolbox and proceed to the next step
46 -1. Connect to first ZUMNET-JBOX in the Crestron Zūm App
103 +1. Connect to each ZUMNET-JBOX in the Crestron Zūm App
104 +1*. Commission room through the app
105 +1**. configure keypad logic
106 +1**. configure occupancy sensor settings
107 +1**. calibrate photocell(s)
108 +1*. Set hostnames for the ZUMNETs.
109 +1**. Zūm discovery will bring in hostnames.
47 47  1. Unique Connection IDs should be automatically assigned to any Zūm Link and Cresnet devices on the ZUMNET-JBOX
48 48  1*. If firmware was out-of-date, then this step should have already been completed
49 49  1*. If unique CIDs are not automatically assigned, connect to the JBOX in Toolbox and give the devices unique CIDs
50 50  1. Configure a static IP address for the ZUMNET-JBOX if there is no DHCP server on the network 
51 51  1*. If firmware was out-of-date, then this step should have already been completed
52 -1*. Note: The SHOWRUNNER™ built-in DHCP server is not meant to be used in production
53 -1*. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
115 +1*. Note: The ShowRunnerCLC™ built-in DHCP server is not meant to be used in production
116 +1*. If the ShowRunnerCLC™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
54 54  1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
55 55  1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
56 56  1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
57 -1*. Full control from SHOWRUNNER™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
58 -1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by SHOWRUNNER™ have static IP addresses and unique CIDs for any hosted devices
120 +1*. Full control from ShowRunnerCLC™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between ShowRunnerCLC™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
121 +1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by ShowRunnerCLC™ have static IP addresses and unique CIDs for any hosted devices
59 59  1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
60 -1. Run the command: ##sr discover zumnet true false##
61 -1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration
62 -1. Run the command: ##sr discover zumnet true true##
63 -1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
64 -1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area
65 -1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
123 +1. If trying to Auto Discover on a job with multiple processors or you are returning to a job where new ZUMNET-JBOXs have been added and you only wish to Auto Discover those new devices, ShowRunnerCLC™ 3.062 and newer allow [[filtering based on hostname or IP address>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Program Configuration.Zūm Discovery.WebHome||anchor="HDiscoveryFilter28ShowRunnerCLC21223.062ornewer29"]] in order to limit the devices that are brought into the ShowRunnerCLC™ configuration
124 +1. Run the command: ##sr discover zumnet true true## to add ZUMNET-JBOXs, connected ZUMLINK devices, and some Cresnet devices (such as Cameo keypads) to the configuration. (Note
125 +1*. This command will update the ShowRunnerCLC™ configuration with: 
126 +1**. One area per claimed ZUMNET-JBOX based on the Room Name set in the app
127 +1**. One ZUMNET-BRIDGE load controller per claimed ZUMNET-JBOX to allow the Zūm Room to communicate its current status (scene, occupancy, etc.) to ShowRunnerCLC™
128 +1**. One entry for each ZUMLINK-KP, ZUMLINK-JBOX, and ZUMLINK occupancy sensor connected to each ZUMNET-JBOX
129 +1***. All devices and loads will be auto-labeled based on their connection information, //not// the names they are given in the Zūm App
130 +1***. Keypads will be brought in as "Remote" type and only follow the logic as defined in the Zūm App, allowing for scheduled enabling/disabling of keypads without adding any additional button functions from ShowRunnerCLC™
131 +1***. Occupancy sensors will be brought in with "Use Hardware Logic" and only follow the logic as defined in the Zūm App
132 +1*. Optionally, run ##sr discover zumnet false true## to only add new ZUMLINK devices to the configuration. **Note that previously added ZUMLINK devices will be added again if their CID has been changed**
133 +1*. Run ##sr discover zumnet true false## to add ZUMNET-JBOXs without bringing in any devices. **Note that if a ZUMNET-JBOX already has an entry in its IP Table, ShowRunnerCLC™ will not claim it.** The ZUMNET-JBOX's IP Table must be cleared in order for it to be claimed by the ShowRunnerCLC™ program
66 66  1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
135 +1. If new Zūm Link hardware has been added, it is not necessary to do a full Auto Discovery to bring the new devices into ShowRunnerCLC™; instead you can just run ##sr discover zumnet false true## to bring in the new Zūm Link devices without claiming any new Zūm Net devices
67 67  
68 68  = Zūm Wireless Discovery =
69 69  
... ... @@ -71,48 +71,49 @@
71 71  
72 72  (% class="box warningmessage" %)
73 73  (((
74 -* Processor with SHOWRUNNER™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
75 -** For SHOWRUNNER™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
143 +* Processor with ShowRunnerCLC™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
144 +** For ShowRunnerCLC™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
76 76  * ZUM-NETBRIDGES must already be acquired to their respective gateway
77 -* SHOWRUNNER™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
146 +* ShowRunnerCLC™ will automatically address any ZUM-NETBRIDGES that do not need have addresses assigned, but will still honor any already addressed devices
78 78  * Disconnect from any RF gateways you may be connected to in Toolbox prior to running the discovery command
79 -* Plug loads will not appear in the SHOWRUNNER™ UI
148 +* Plug loads will not appear in the ShowRunnerCLC™ UI
149 +* Newer GWEXER firmware enables SSL by default. Follow the instructions at [[SSL User Configuration>>doc:SHOWRUNNER™ User Guide & Wiki.SHOWRUNNER™ Appendix.SSL User Configuration.WebHome]] and manually add the IP Table entries on the GWEXER
80 80  )))
81 81  
82 82  (% class="box infomessage" id="HCaution:" %)
83 83  (((
84 -**Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Discovery
154 +**Note:** ShowRunnerCLC™ has two different approaches for Zūm Wireless Discovery
85 85  
86 -1. **Manual RF Gateway Assignment** - SHOWRUNNER™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
87 -1. **Claim All RF Gateways** - SHOWRUNNER™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different SHOWRUNNER™ or other Crestron systems on the same local network.
156 +1. **Manual RF Gateway Assignment** - ShowRunnerCLC™ can be told which gateways it should scan. Use this approach if you have gateways that are used by multiple systems on the same local network.
157 +1. **Claim All RF Gateways** - ShowRunnerCLC™ will find all CEN-GWEXERs [ZUMNET-GATEWAY] on the network and will claim them as its own. **DO NOT** use this method if there are gateways used by different ShowRunnerCLC™ or other Crestron systems on the same local network.
88 88  )))
89 89  
90 90  == Manual RF Gateway Assignment Instructions ==
91 91  
92 -Use this method if you have multiple SHOWRUNNER™ instances on the same network or have gateways used by other Crestron systems.
162 +Use this method if you have multiple ShowRunnerCLC™ instances on the same network or have gateways used by other Crestron systems.
93 93  
94 94  * Connect to the processor's console with Toolbox or your favorite SSH client.
95 95  * Type ##sr devmgr ethernet query## and press enter. This queries the local network for RF Gateways.
96 96  * Type ##sr devmgr ethernet show devices## and press enter. This displays all found Crestron ethernet devices.
97 -* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. SHOWRUNNER™ will auto-assign an IP-ID. After all gateways have been claimed by SHOWRUNNER™, proceed to the next step.
167 +* For each gateway that you'd like this instance of SHOWRUNNER™ to use, use the hostname from the table of found ethernet devices. For example if the gateway Hostname is CEN-GWEXER-9E6ADA type ##sr ethernet device claim CEN-GWEXER-9E6ADA##. ShowRunnerCLC™ will auto-assign an IP-ID. After all gateways have been claimed by ShowRunnerCLC™, proceed to the next step.
98 98  * Type ##sr discover zummesh false## and press enter.
99 99  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
100 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
101 -* Type ##progreset## and press enter to restart SHOWRUNNER
102 -* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
170 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
171 +* Type ##progreset## and press enter to restart ShowRunnerCLC
172 +* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
103 103  * Once completed SHOWRUNNER™ is now ready for full Zūm control
104 104  
105 105  == Claim All RF Gateways Instructions ==
106 106  
107 -Use this method when you have a single SHOWRUNNER™ instance on a local network with all gateways being used for SHOWRUNNER™.
177 +Use this method when you have a single ShowRunnerCLC™ instance on a local network with all gateways being used for ShowRunnerCLC™.
108 108  
109 109  * Connect to the processor's console with Toolbox or your favorite SSH client.
110 110  * Type ##sr discover zummesh true## and press enter.
111 111  * Status messages and the results will be displayed on the console. The process should take about 3 minutes.
112 -* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, SHOWRUNNER™ must be restarted to complete the acquire process.
113 -* Type ##progreset## and press enter to restart SHOWRUNNER
114 -* Once SHOWRUNNER™ has finished restarting type ##sr discover zummesh false## and press enter. SHOWRUNNER™ will be able to acquire the loads attached to the Zūm rooms at this point.
115 -* Once completed SHOWRUNNER™ is now ready for full Zūm control
182 +* When the discovery is finished type ##sr save## and press enter to save the updated config. Due to an unknown quirk that we are looking into, ShowRunnerCLC™ must be restarted to complete the acquire process.
183 +* Type ##progreset## and press enter to restart ShowRunnerCLC
184 +* Once ShowRunnerCLC™ has finished restarting type ##sr discover zummesh false## and press enter. ShowRunnerCLC™ will be able to acquire the loads attached to the Zūm rooms at this point.
185 +* Once completed ShowRunnerCLC™ is now ready for full Zūm control
116 116  
117 117  == Examples ==
118 118