Summary

Details

Page properties
Content
... ... @@ -1,8 +6,3 @@
1 -(% class="box errormessage" %)
2 -(((
3 -WARNING: Cresnet Discovery is not currently working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE. Discovery must be fixed before SHOWRUNNER™ can auto-discover hardware.
4 -)))
5 -
6 6  (% class="box warningmessage" %)
7 7  (((
8 8  This article is about automatically building a SHOWRUNNER™ configuration using the Zūm Discovery feature of SHOWRUNNER™. For instructions on configuring Zūm Wired rooms using the Crestron Zūm App, see [[this page>>SHOWRUNNER™ Setup Guide.Wiring Guide.Zūm Wired System Overview.Crestron Zūm App Overview.WebHome]].
... ... @@ -21,10 +21,10 @@
21 21  
22 22  == Notes and Limitations ==
23 23  
24 -(% class="box warningmessage" %)
19 +(% class="box errormessage" %)
25 25  (((
26 26  * SHOWRUNNER™ version 3.014 or newer required
27 -* Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
22 +* Zūm Wired firmware version 1.02.10 or greater required
28 28  * Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
29 29  * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
30 30  * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
... ... @@ -53,8 +53,6 @@
53 53  1*. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
54 54  1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
55 55  1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
56 -1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
57 -1*. Full control from SHOWRUNNER™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
58 58  1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by SHOWRUNNER™ have static IP addresses and unique CIDs for any hosted devices
59 59  1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
60 60  1. Run the command: ##sr discover zumnet true false##
... ... @@ -63,13 +63,14 @@
63 63  1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
64 64  1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area
65 65  1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
66 -1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
59 +1. Put all ZUMNET-JBOXs into CNET mode in order to allow full control from SHOWRUNNER™
60 +1*. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
67 67  
68 68  = Zūm Wireless Discovery =
69 69  
70 70  == Notes and Limitations ==
71 71  
72 -(% class="box warningmessage" %)
66 +(% class="box errormessage" %)
73 73  (((
74 74  * Processor with SHOWRUNNER™ version 2.190 or newer must be running on the same network as the gateway(s) to be acquired
75 75  ** For SHOWRUNNER™ versions prior to 3.014 and newer, replace **##sr discover zummesh##** commands with **##sr discover zum##**
... ... @@ -79,7 +79,7 @@
79 79  * Plug loads will not appear in the SHOWRUNNER™ UI
80 80  )))
81 81  
82 -(% class="box infomessage" id="HCaution:" %)
76 +(% class="box warningmessage" id="HCaution:" %)
83 83  (((
84 84  **Note:** SHOWRUNNER™ has two different approaches for Zūm Wireless Discovery