... ... @@ -8,6 +8,8 @@
8 8  {{toc/}}
9 9  {{/box}}
10 10  
11 +(% class="row" %)
12 +(((
11 11  If Zūm Wired or Wireless devices have been configured using Crestron's Zūm App, then it is possible to automatically build a SHOWRUNNER™ configuration file using the Zūm Discovery feature that is built into SHOWRUNNER™.
12 12  
13 13  There are certain pre-requisites and limitations when building a SHOWRUNNER™ configuration this way, and it may sometimes be necessary make some adjustments to the final configuration, such as changing keypad types and moving loads between areas.
... ... @@ -19,7 +19,7 @@
19 19  (% class="box errormessage" %)
20 20  (((
21 21  * SHOWRUNNER™ version 3.014 or newer required
22 -* Zūm Wired firmware .puf version 1.02.10 or greater required (ZUMNET-JBOX installed minimum version 1.001.00081)
24 +* Zūm Wired firmware version 1.02.10 or greater required
23 23  * Disconnect from any ZUMNET devices you may be connected to in Toolbox prior to running the discovery commands
24 24  * Cresnet devices landed on Zūm Link will not be discovered (Crestron bug expected to be corrected in a future firmware release)
25 25  * One area will be created per ZUMNET-JBOX; if there are more areas than ZUMNET-JBOXs, additional areas must be created manually
... ... @@ -48,17 +48,16 @@
48 48  1*. If the SHOWRUNNER™ built-in DHCP server was used to assign IP addresses to devices, it is still necessary to give those devices static IP addresses
49 49  1. Optionally, manually configure the ZUMNET-JBOX IP table to point at the processor if you want to keep track of which ZUMNET-JBOX is at each IP-ID
50 50  1*. If you do not manually configure the IP table, then SHOWRUNNER™ will automatically configure the IP-ID for each ZUMNET-JBOX during discovery
51 -1. Set the ZUMNET-JBOX into either Zūm ("App") mode or CNET mode as required for the program
52 -1*. Full control from SHOWRUNNER™ is only possible if all ZUMNET-JBOXs are in CNET mode. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
53 53  1. Repeat from step 3 until all ZUMNET-JBOXs that are to be controlled by SHOWRUNNER™ have static IP addresses and unique CIDs for any hosted devices
54 54  1. Disconnect from any ZUMNET-JBOXs and then connect to the processor in Toolbox
55 55  1. Run the command: ##sr discover zumnet true false##
56 -1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding IP Devices to the configuration
56 +1*. This command tells SHOWRUNNER™ to discover all ZUMMNET-JBOXs on the network, configure their IP tables, and then add corresponding areas and loads to the configuration
57 +1*. One area will be created per ZUMNET-JBOX
57 57  1. Run the command: ##sr discover zumnet true true##
58 -1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware (including the internal ZUMNET-JBOX load controller) on the previously discovered Zūm Net devices and then add corresponding areas, loads, sensors, etc. to the configuration
59 -1**. One area will be created per ZUMNET-JBOX, and all hardware attached to that ZUMNET-JBOX will be assigned to that area
59 +1*. This command tells SHOWRUNNER™ to discover all Zūm Link hardware on the previously discovered Zūm Net devices
60 60  1*. This command **does not** bring in Cresnet devices: those must be added to the configuration manually until this issue is fixed in the Zūm Wired firmware
61 -1. If all steps have been performed successfully, then you should be able to use the ##sr show area##, ##sr show load##, ##sr show keypad##, and ##sr show occ## commands to see that the ZUMNET and ZUMLINK hardware has been discovered correctly.
61 +1. Put all ZUMNET-JBOXs into CNET mode in order to allow full control from SHOWRUNNER™
62 +1*. Odd behavior may result from conflicts between SHOWRUNNER™ and internal logic if the ZUMNET-JBOXs are not put into CNET mode
62 62  
63 63  = Zūm Wireless Discovery =
64 64  
... ... @@ -303,3 +303,4 @@
303 303  Removed Loads: 0
304 304  Zum Discovery Finished
305 305  }}}
307 +)))