1 | The foundations of a quick, easy, and trouble-free startup are laid before the control hardware even arrives onsite. Meeting with the electrical contractor prior to construction is important to establish a good working relationship, explain the requirements for a Crestron lighting control installation, and to exchange contact information so that any technical questions or concerns can be addressed prior to startup. | ||
2 | |||
3 | Though a pre-construction site-visit may seem like a wasted expense, by communicating expectations and requirements to the electrical contractor prior to startup you are actually able to save time and headache on-site. For large jobs especially, taking the time to ensure a proper installation will save hours or days during startup. Any time spent by a technician on-site tracking down serial numbers or troubleshooting/correcting a poor installation is a waste that could have been avoided with good communication and instruction prior to and throughout the installation process. | ||
4 | |||
5 | Covering these important topics with the electrical contractor during the pre-construction phase is critical to smooth ShowRunnerCLC™ startups. | ||
6 | |||
7 | Pre-construction topics to cover: | ||
8 | |||
9 | * [[Wiring and Installation>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.WebHome]] | ||
10 | ** Do not power up panels until installation is complete and wiring is verified safe to connect | ||
11 | ** [[Cresnet wiring>>doc:SHOWRUNNER™ Setup Guide.Wiring Guide.Wiring Overview.Cresnet.WebHome]] (for jobs with Cresnet) | ||
12 | *** (% style="color:green" %)**DO**(%%) check for shorts before landing at the panel | ||
13 | *** (% style="color:green" %)**DO**(%%) land the shield with COM at the panel | ||
14 | *** (% style="color:green" %)**DO**(%%) splice through and insulate shield in the field | ||
15 | *** (% style="color:green" %)**DO**(%%) use wire nuts for Cresnet splices | ||
16 | *** (% style="color:red" %)**DO NOT**(%%) use lever-nuts for Cresnet splices | ||
17 | *** (% style="color:red" %)**DO NOT**(%%) leave copper showing at terminations | ||
18 | *** (% style="color:red" %)**DO NOT**(%%) excessively strip back the teal-yellow jacket | ||
19 | ** [[Ethernet terminations>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Hardware and Installation.Ethernet Wiring Overview.WebHome]] (where the EC is terminating the Ethernet) | ||
20 | *** (% style="color:green" %)**DO**(%%) use standard, non-passthrough RJ-45 connectors | ||
21 | *** (% style="color:green" %)**DO**(%%) use T568B Pin-Out | ||
22 | *** (% style="color:red" %)**DO NOT**(%%) use EZ-style passthrough RJ-45 connectors | ||
23 | *** (% style="color:red" %)**DO NOT**(%%) exceed 100m/328' cable length | ||
24 | ** [[Zūm Wired wiring>>doc:SHOWRUNNER™ Setup Guide.Troubleshooting Guide.Hardware and Installation.Zūm Wired Wiring Overview.WebHome]] (for Zūm Wired jobs) | ||
25 | *** (% style="color:green" %)**DO**(%%) use standard, non-passthrough RJ-45 connectors | ||
26 | *** (% style="color:green" %)**DO**(%%) use T568B Pin-Out | ||
27 | *** (% style="color:red" %)**DO NOT**(%%) use EZ-style passthrough RJ-45 connectors | ||
28 | *** (% style="color:red" %)**DO NOT**(%%) exceed 100m/328' cable length | ||
29 | *** (% style="color:red" %)**DO NOT**(%%) mix up Zūm Net and Zūm Link cables | ||
30 | ** Follow the load schedule | ||
31 | * Serial number collection | ||
32 | ** SNs should be collected for all networked devices (all Cresnet devices and Zūm Wired devices) | ||
33 | *** If possible, SNs should be provided prior to startup. This way they can be put into the configuration prior to arriving on-site | ||
34 | ** The EC does not need to collect SNs for non-system devices (e.g. Crestron NS occupancy sensors, Steinel occupancy sensors, LDL photocells, and GLPPA-KP keypads | ||
35 | ** It is important to not just have a list of SNs on-site, but to be able to associate individual SNs with specific installed devices | ||
36 | ** The easiest way to do this is to write the SNs of installed devices on the floor plans or riser diagram as they are installed | ||
37 | * MAC address collection (optional) | ||
38 | ** Collecting MAC addresses is redundant if serial numbers are provided | ||
39 | * Establish expectations for what "ready to commission" means by sharing the [[site readiness checklist>>doc:SHOWRUNNER™ Setup Guide.SHOWRUNNER™ Installation Guide.Preparation.Site Readiness Checklist.WebHome]] |