Changes for page Steinel GLA-IR-QUATTRO-HD-COM1-24
Last modified by Alexander Mott on 2022/09/20 17:22
From version 7.1
edited by Craig Lewis
on 2020/05/15 16:56
on 2020/05/15 16:56
Change comment:
There is no comment for this version
To version 8.1
edited by Craig Lewis
on 2020/05/15 16:59
on 2020/05/15 16:59
Change comment:
There is no comment for this version
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -2,9 +2,9 @@ 2 2 3 3 === Note on GLA-IR-QUATTRO-HD-COM1-24 Power Draw === 4 4 5 -The listed power draw for GLA-IR-QUATTRO-HD-COM1-24 sensors is 32mA at 24VDC, however Chief Integrations' testing with shipped hardware shows the real-world power draw to be closer to 20mA. While GLPP modules are able to provide 150mA at 24VDC for sensors, applications with up to 4 have been shown to work. (While calculations based on measured power draw would allow for up to 7 sensors on one GLPP, Chief Integrations cannot recommend exceeding manufacturer specifications)5 +The listed power draw for GLA-IR-QUATTRO-HD-COM1-24 sensors is 32mA at 24VDC, however Chief Integrations' testing with shipped hardware shows the real-world power draw to be closer to 20mA. While GLPP modules are able to provide 150mA at 24VDC for sensors, applications with up to 4 have been shown to work. 6 6 7 -thi sis sufficientfor real-world applicationsinvolving4GLA-IR-QUATTRO-HD-COM1-24occupancysensors.7 +Note: While calculations based on measured power draw would allow for up to 7 sensors on one GLPP, Chief Integrations cannot recommend exceeding manufacturer specifications. 8 8 9 9 === Detailed Analysis === 10 10