... ... @@ -2,9 +2,9 @@
2 2  
3 3  === Note on GLA-IR-QUATTRO-HD-COM1-24 Power Draw ===
4 4  
5 -The listed power draw for GLA-IR-QUATTRO-HD-COM1-24 sensors is 32mA at 24VDC, however Chief Integrations' testing with shipped hardware shows the real-world power draw to be closer to 20mA. While GLPP modules are able to provide 150mA at 24VDC for sensors, this is sufficient for real-world applications involving 5 GLA-IR-QUATTRO-HD-COM1-24 occupancy sensors.
5 +The listed power draw for GLA-IR-QUATTRO-HD-COM1-24 sensors is 32mA at 24VDC, however Chief Integrations' testing with shipped hardware shows the real-world power draw to be closer to 20mA. While GLPP modules are able to provide 150mA at 24VDC for sensors, applications with up to 4 have been shown to work. (While calculations based on measured power draw would allow for up to 7 sensors on one GLPP, Chief Integrations cannot recommend exceeding manufacturer specifications)
6 6  
7 -As such, Chief Integrations recommends adding a TR-100 or other external power supply if more than two sensors are required to be added to one GLPP.
7 +this is sufficient for real-world applications involving 4 GLA-IR-QUATTRO-HD-COM1-24 occupancy sensors.
8 8  
9 9  === Detailed Analysis ===
10 10