6 6  The listed power draw for GLS-ODT-C-NS sensors is 45mA at 24VDC, however Chief Integrations' testing with shipped hardware shows the real-world power draw to be closer to 60mA. While GLPP modules are able to provide 150mA at 24VDC for sensors, this is insufficient for real-world applications involving more than two GLS-ODT-C-NS occupancy sensors.
7 7  
8 -As such, Chief Integrations recommends adding a TR-100 or other external power supply if more than two sensors are required to be added to one GLPP.
8 +As such, Chief Integrations recommends adding a GLA-TR-100 or other external power supply if more than two sensors are required to be added to one GLPP.