Changes for page GLS-ODT-C-NS and CN
Last modified by Alexander Mott on 2021/12/08 00:15
From version 8.1
edited by Craig Lewis
on 2020/05/15 16:45
on 2020/05/15 16:45
Change comment:
There is no comment for this version
To version 9.1
edited by Craig Lewis
on 2020/05/15 16:50
on 2020/05/15 16:50
Change comment:
There is no comment for this version
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -5,7 +5,7 @@ 5 5 6 6 The listed power draw for GLS-ODT-C-NS sensors is 45mA at 24VDC, however Chief Integrations' testing with shipped hardware shows the real-world power draw to be closer to 60mA. While GLPP modules are able to provide 150mA at 24VDC for sensors, this is insufficient for real-world applications involving more than two GLS-ODT-C-NS occupancy sensors. 7 7 8 -As such, Chief Integrations recommends adding a TR-100 or other external power supply if more than two sensors are required to be added to one GLPP. 8 +As such, Chief Integrations recommends adding a GLA-TR-100 or other external power supply if more than two sensors are required to be added to one GLPP. 9 9 10 10 === Detailed Analysis === 11 11