... ... @@ -123,7 +123,11 @@
123 123  Zūm Link limitations:
124 124  
125 125  * Do not exceed 31 ZUMLINK-* and Cresnet devices on a single ZUMNET-JBOX-* device
126 -* Do not exceed 2 ZUMLINK-OCC-* sensors or non-system sensors per ZUMNET/ZUMLINK-JBOX-* room
127 -** Each ZUMNET/ZUMLINK-JBOX-* is limited to 24 V, 85 mA output shared across their Zūm Link ports and sensor inputs
128 -** Power is said to be additive between boxes,
126 +* Do not exceed 85mA of 24VDC power consumption per ZUMNET/ZUMLINK-JBOX-* device on the Zūm Link bus
127 +** Each ZUMNET/ZUMLINK-JBOX-* is limited to 85mA of 24VDC output shared across their Zūm Link ports and sensor inputs
128 +** Power is shared between ZUMNET/ZUMLINK-JBOX-* devices on a single Zūm Link bus, so adding more ZUMNET/ZUMLINK-JBOX-* devices to a network increases the available power
129 +** ZUMLINK-IR-QUATTRO-HD-DLS/RLY occupancy sensors are rated at 32mA of power consumption
130 +** Other ZUMLINK-OCC-* sensors are rated at 25mA of power consumption each
131 +** ZUMLINK-KP keypads do not have a listed power consumption, but designing for approximately 20mA is safe
132 +* Available power on the Zūm Link bus can be increased by adding additional ZUMLILNK-JBOX-* devices, or by adding a separate power pack to provide power for non-system sensors or Cresnet devices on the Zūm Link bus
129 129  )))