Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -*Crestron Zūm Wired and SHOWRUNNER™
1 +**Crestron Zūm Wired and SHOWRUNNER™
Content
... ... @@ -1,3 +1,8 @@
1 +(% class="box successmessage" %)
2 +(((
3 +Page for showrunner feature comparison, reasons for using showrunner, etc.; should also include information from old
4 +)))
5 +
1 1  (% class="box errormessage" %)
2 2  (((
3 3  n/a
... ... @@ -181,6 +181,21 @@
181 181  |ZWMS (Zum Wired Master/Slave Mode)|MASTER|MASTER|MASTER or SLAVE
182 182  |ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|ZUM|ZUM
183 183  
189 +=== Caveats ===
190 +
191 +* Consult Chief Integrations to verify sequence of operations if there are any concerns.
192 +* Additional caveats:
193 +** --Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
194 +** --Raw Occupancy reporting does not work. A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner. ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
195 +** Cresnet Discovery is not working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE. Discovery must be fixed before ShowRunner can auto-discover hardware.
196 +
197 +=== FAQ: ===
198 +
199 +* I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
200 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB. A DIN-AP4 is not required. Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails. [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]//
201 +* Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
202 +//If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
203 +
184 184  == Out-of-the-Box vs App vs Default Program vs Custom Program ==
185 185  
186 186  Below is a Feature Comparison Table taken from the v3.05.02 Zūm Wired firmware release notes.