... ... @@ -63,7 +63,7 @@
63 63  
64 64  (% class="box errormessage" %)
65 65  (((
66 -need to update this section
66 +need to verify information is up to date for this section
67 67  )))
68 68  
69 69  The below table compares some SHOWRUNNER exclusive features against networked systems using the default program and standalone systems using Zūm App mode.
... ... @@ -181,6 +181,19 @@
181 181  |ZWMS (Zum Wired Master/Slave Mode)|MASTER|MASTER|MASTER or SLAVE
182 182  |ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|ZUM|ZUM
183 183  
184 +=== Caveats ===
185 +* Consult Chief Integrations to verify sequence of operations if there are any concerns.
186 +* Additional caveats:
187 +** --Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
188 +** --Raw Occupancy reporting does not work. A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner. ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
189 +** Cresnet Discovery is not working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE. Discovery must be fixed before ShowRunner can auto-discover hardware.
190 +=== FAQ: ===
191 +* I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
192 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB. A DIN-AP4 is not required. Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails. [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]//
193 +* Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
194 +//If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
195 +
196 +
184 184  == Out-of-the-Box vs App vs Default Program vs Custom Program ==
185 185  
186 186  Below is a Feature Comparison Table taken from the v3.05.02 Zūm Wired firmware release notes.