... ... @@ -1,1 +1,1 @@
1 -*Crestron Zūm Wired and SHOWRUNNER™
1 +**Crestron Zūm Wired and SHOWRUNNER™
Content
... ... @@ -59,8 +59,13 @@
59 59  
60 60  = Feature Comparison Tables =
61 61  
62 -== SHOWRUNNER ==
62 +== SHOWRUNNER vs Default Program vs Standalone ==
63 63  
64 +(% class="box errormessage" %)
65 +(((
66 +need to verify information is up to date for this section
67 +)))
68 +
64 64  The below table compares some SHOWRUNNER exclusive features against networked systems using the default program and standalone systems using Zūm App mode.
65 65  
66 66  |=Feature|=(((
... ... @@ -176,6 +176,21 @@
176 176  |ZWMS (Zum Wired Master/Slave Mode)|MASTER|MASTER|MASTER or SLAVE
177 177  |ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|ZUM|ZUM
178 178  
184 +=== Caveats ===
185 +
186 +* Consult Chief Integrations to verify sequence of operations if there are any concerns.
187 +* Additional caveats:
188 +** --Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
189 +** --Raw Occupancy reporting does not work. A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner. ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
190 +** Cresnet Discovery is not working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE. Discovery must be fixed before ShowRunner can auto-discover hardware.
191 +
192 +=== FAQ: ===
193 +
194 +* I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
195 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB. A DIN-AP4 is not required. Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails. [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]//
196 +* Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
197 +//If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
198 +
179 179  == Out-of-the-Box vs App vs Default Program vs Custom Program ==
180 180  
181 181  Below is a Feature Comparison Table taken from the v3.05.02 Zūm Wired firmware release notes.