Last modified by Alexander Mott on 2023/12/08 18:49

From version 12.1
edited by Alexander Mott
on 2023/03/27 21:34
Change comment: There is no comment for this version
To version 22.1
edited by Alexander Mott
on 2023/12/08 18:49
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -*Crestron Zūm Wired and SHOWRUNNER™
1 +**Crestron Zūm Wired and SHOWRUNNER™
Content
... ... @@ -1,3 +1,8 @@
1 +(% class="box successmessage" %)
2 +(((
3 +Page for showrunner feature comparison, reasons for using showrunner, etc.; should also include information from old
4 +)))
5 +
1 1  (% class="box errormessage" %)
2 2  (((
3 3  n/a
... ... @@ -23,25 +23,23 @@
23 23  
24 24  Lorem
25 25  
26 -== Ease of Start-Up ==
31 +== Exclusive Features ==
27 27  
28 -
29 29  Lorem
30 30  
31 -== Exclusive Features ==
35 +== Suitable for a Range of Applications ==
32 32  
33 33  Lorem
34 34  
35 -== Advanced Reporting Features ==
39 +== Ease of Start-Up and Documentation ==
36 36  
37 -- see all hardware online status from one place
41 +Every SHOWRUNNER™ job comes with a number of Chief Tools™ to simplify the start-up process and enable Agents and Technicians to for networked Zūm Wired systems. These tools include:
38 38  
39 -- records of device/hardware functionality
43 +* SRTakeoff spreadsheet provides the Technician with one location to view device addresses, record serial numbers, and track any issues discovered during start-up
44 +* Zūm Wired Load Script generator enables technicians to easily create load scripts to streamline necessary configuration tasks based on the DeviceSummary.txt generated by Toolbox
40 40  
41 -== Suitable for a Range of Applications ==
46 +See the [[Starting Up Zūm Wired with SHOWRUNNER™>>doc:Design Guide.Hardware Design Guide.Crestron Zum Wired.Crestron Zum Wired Overview.WebHome||anchor="HStart-UpGuide"]] page for more information on starting up Zūm Wired systems with SHOWRUNNER™.
42 42  
43 -Lorem
44 -
45 45  == Support and Continued Development ==
46 46  
47 47  Lorem
... ... @@ -59,7 +59,188 @@
59 59  
60 60  SHOWRUNNER™
61 61  
62 -= Feature Comparison Table =
65 += Feature Comparison Tables =
63 63  
64 -Lorem
67 +== SHOWRUNNER™ vs Default Program vs Standalone ==
68 +
69 +(% class="box errormessage" %)
70 +(((
71 +need to verify information is up to date for this section
65 65  )))
73 +
74 +The below table compares some SHOWRUNNER exclusive features against networked systems using the default program and standalone systems using Zūm App mode.
75 +
76 +|=Feature|=(((
77 +**Networked**
78 +
79 +**(**SHOWRUNNER™**)**
80 +)))|=(((
81 +**Networked**
82 +
83 +**(HUB4)**
84 +)))|=(((
85 +**Zūm App**
86 +
87 +**(Standalone)**
88 +)))
89 +|(% colspan="4" %)**Hardware Requirements**
90 +|Requires ZUMNET-JBOX-*|Y|Y|N
91 +|Requires 3 or 4-Series Control System|Y (Can use a number of different 3 and 4-Series processors)|Y (Requires ZUM-HUB4)|N
92 +|Requires Physical Presence in Room to Change Scenes|N|TBD|Y
93 +|Maximum Rooms|TBD|1000|N/A
94 +|(% colspan="4" %)**User Interfaces**
95 +|Web Browser|(((
96 +Crestron SmartGraphics XPanel
97 +HTML5 UI
98 +)))|HTML5 UI|N
99 +|iOS/Android|Y, Crestron App (Paid Upgrade) or HTML5 UI (Device Web Browser)|N|Y*
100 +|Touchscreens (Crestron TSW series)|Y|N|N
101 +|(% colspan="4" %)**Features**
102 +|Scene Recall|Y|Y|Y
103 +|Override Fade Time for Scene Recall|Y|TBD|TBD
104 +|Scene Save|Y|TBD|Y
105 +|Load Control|Y|TBD|Y
106 +|Demand Response|Y|Y|N
107 +|Enable/Disable Occupancy|Y|Y|Y
108 +|Override Occupancy Logic|Y|TBD|N
109 +|Override|Y|TBD|N/A
110 +|Plug Load On/Off|Y|Y|By Hardware
111 +|Integration with Non-Zūm Crestron Hardware|Y|N|N
112 +|Custom Zūm Keypad Programming|Y|TBD|Y, within the limits of the hardware
113 +|New Feature Release Cycle|Aggressive|6-12 months|6-12 months
114 +|Room Organization|(((
115 +Organize According to Defined Nodes, multiple levels
116 +Categorization to Filter by Tag
117 +)))|Category/Room|(((
118 +N/A
119 +)))
120 +|Room Discovery|Automatic Discovery of ZUMNET and ZUMLINK devices (Pending)|Automatic Discovery of ZUMNET and ZUMLINK devices|N/A
121 +|Network Topology|(((
122 +* Flat
123 +* Single Handoff to LAN w/ Control Subnet
124 +(Requires CP4N/AV4/PRO4)
125 +)))|Single Handoff to LAN w/ Control Subnet|N/A
126 +|Network Addressing|(((
127 +* Manual
128 +* Customer (DHCP or Manual)
129 +* DHCP: Control Subnet (Requires CP4N/AV4/PRO4)
130 +)))|Control Subnet|N/A
131 +|Firmware Updates|PUF Tool
132 +Automatic Support on Roadmap|Automatic, Internet Connection Required|N/A
133 +|Floorplans|Y|N|N/A
134 +|(% colspan="4" %)**Calendar/Scheduling**
135 +|Logic Type|Event Driven
136 +Profile Support (Under Development)|Pattern assigned to Category|N/A
137 +|Astronomical Clock|Y|Y, Per Category|N/A
138 +|Holidays|Pattern|Hard Coded|N/A
139 +|Custom Patterns|Y, Advanced Scheduler License|N|N/A
140 +|(% colspan="4" %)**Integrations**
141 +|A/V Integration: API|Y|Limited|N/A
142 +|A/V Integration: Crestron EISC|Y|N|N/A
143 +|A/V Integration: RS-232|Y|TBD|N/A
144 +|BACNET|Y, SHOWRUNNER™ and Crestron Licenses Needed|Y|N/A
145 +|BACNET Features|(((
146 +Per Area Status:
147 +Active Scene
148 +Occupied
149 +Occupancy Enabled
150 +Individual Load Level
151 +Photocell Level (per Photocell)
152 +Plug Loads Enabled
153 +System:
154 +Demand Response Enabled
155 +System Wide Override (Panic/Emergency)
156 +~* More Features added upon request
157 +)))|(((
158 +Per Room Status:
159 +Online
160 +On
161 +Occupied
162 +Daylighting Active
163 +Device Battery is Low
164 +Plug Loads Enabled
165 +Occupancy Sensor Enabled
166 +Current Daylight Level
167 +Active Scene
168 +\\System:
169 +Demand Response Enabled
170 +)))|N/A
171 +|BACNET Settings Scope
172 +(What Points are Exposed)|Per Area|Global|N/A
173 +|BACNET Points Supported|Depends on Crestron License and Hardware|1000|N/A
174 +|Crestron Fusion|Y|N|N/A
175 +|Export to Zūm Floor Hub|Y, Licensed|N/A|N/A
176 +|GLPAC|Y|N|N/A
177 +|System to System Link|Y|N|N/A
178 +|Minimum ZUM-NET Firmware|(((
179 +CNET Mode: ZUM-WIRED 1.02.10 puf
180 +ZUM Mode: ZUM-WIRED 1.xx.xxx puf (Pending)
181 +)))|See Crestron, expected to be v1.01|See Crestron, expected to be v1.01
182 +|Minimum SHOWRUNNER™ Version|(((
183 +CNET Mode: 3.016
184 +ZUM Mode: TBD
185 +)))|N/A|N/A
186 +|ZWMS (Zum Wired Master/Slave Mode)|MASTER|MASTER|MASTER or SLAVE
187 +|ZWMODE|CNET or ZUM (ZUM Support Pending official release from Crestron)|ZUM|ZUM
188 +
189 +=== Caveats ===
190 +
191 +* Consult Chief Integrations to verify sequence of operations if there are any concerns.
192 +* Additional caveats:
193 +** --Occupancy status is not reported to ShowRunner when ZUMNET/ZUMLINK JBOXs come online. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
194 +** --Raw Occupancy reporting does not work. A delay of 5 seconds to 5 minutes between sensor vacancy and reported vacancy to ShowRunner. ShowRunner attempts to set 30 seconds (v3.003 to v3.009) or 5 seconds (v3.010 and later) but it is not always honored. This has been acknowledged as a bug by Crestron in firmware v1.001.054 and v1.00.009 and is pending a fix from Crestron.-- Fixed in 1.02.010 firmware and Device Database 200.150.002, ShowRunner 3.016 has been updated with these fixes from Crestron.
195 +** Cresnet Discovery is not working on ZUMNET-JBOXs. Crestron has acknowledged a fix has been sent to QE. Discovery must be fixed before ShowRunner can auto-discover hardware.
196 +
197 +=== FAQ: ===
198 +
199 +* I want to have a single connection to the building and have all of my Crestron devices on the Control Subnet (same topology as a ZUM-FLOOR-HUB) and use ShowRunner™ Total Control?
200 +//Use a CP4N in lieu of the ZUM-FLOOR-HUB. A DIN-AP4 is not required. Crestron can supply a DIN-EN-6X18 with CEN-SW-POE-16 and CP4N racked in a 2RU mount plus 3 DIN rails. [[See Design Details.>>doc:Design Guide.Hardware Design Guide.Crestron Zūm Wired.Design to co-locate a CP4N and CEN-SWPOE-16 in the Same DIN-EN Cabinet.WebHome]]//
201 +* Do I need a Crestron BACnet license when using ShowRunner for BACnet integration?
202 +//If over 50 BACnet points are needed then a license (SW-3SERIES-BACNET-50+) will be needed for each Crestron processor that will provide BACnet points to the BMS.//
203 +
204 +== Out-of-the-Box vs App vs Default Program vs Custom Program ==
205 +
206 +Below is a Feature Comparison Table taken from the v3.05.02 Zūm Wired firmware release notes.
207 +
208 +(% class="table-condensed" %)
209 +|**Feature**|**Out of the Box Functionality**|(((
210 +**Zūm App**
211 +
212 +**(Standalone)**
213 +)))|(((
214 +**Networked**
215 +
216 +**(HUB4)**
217 +)))|**Custom Prog.**|**Notes**
218 +|Keypads|Scn recall / OFF|*|*|*|Affect all load controllers excluding Plug controllers
219 +|Presence detectors (Occ sensors)|Scn 1 / Scn 16|*|*|*|Presence detectors affect all load controllers
220 +|Programmable scenes| |✓|*|*|
221 +|Occupancy/Vacancy logic| |✓|*|*|
222 +|Daylight Harvesting| |✓|*|*|J-box analog input support only, ZUMLINK- Daylight sensor via custom programming only.
223 +|Customized Button Functions*
224 +(Tap/Double-Tap/ Hold)| |✓|*|*|none, Off, On, Toggle, Scene 1-16, Export button to Hub
225 +|Create a room configuration Template| |✓|*|*|
226 +|Apply room configuration template| |✓|✓| |Identical hardware rooms required
227 +|Universal 2-wire phase dimming up to 16A| |✓|*|*|ZUMLINK-EXP-DIMU support & Zūm App discovery/configuration
228 +|DALI addressing, Broadcast and groups
229 +support (Zūm Mode)| |✓|*|*|Allows control as Broadcast or 16 DALI Groups
230 +|Device Firmware updating via Zūm APP(BLE).| |✓| | |Requires primary controller at ver. 1.2.60
231 +|DALI addressing and DALI group support (CNET Mode)| | | |✓|Allows addressing, grouping and control of 16 Dali Groups using Simpl #, Simpl Windows
232 +|CNET / Zūm Mode Auto Switch| | | |✓|Automatically switches from CNET to Zum Mode when control system goes offline
233 +|Load shedding| | |✓|*|
234 +|Global/Multi/Cross-room KP| | |✓|*|Scenes, plug load and Occupancy enable/disable
235 +|Timeclock event triggers| | |✓|*|
236 +|DALI Type 6 TC| | | |✓|
237 +|DALI Type 8 TC| | | |✓|
238 +|Touch screen| | |*|✓|Hub4 support with mirror room modules
239 +|Shades| | | |✓|
240 +|AV integration| | |*|✓|Hub4 support with mirror room modules
241 +|Energy Monitoring| | | |✓|
242 +|(((
243 +Floor Map
244 +
245 +* denotes that can be used but not required to achieve functionality
246 +)))| | |*|✓|Hub4 support with mirror room modules
247 +)))
248 +
249 +